 | NEMA Contactors & Starters | 11 | |
| 
 | 
 | 
 | 
 | 
 | 
 | |||
| 
 | 
 | 
 | 
 | 
 | 
 | |||
| September 2003 | IT.  | |||||||
| 
 | ||||||||
| Technical Data and Specifications | 
 | |||||||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | ||
| 
 | 
 | |||||||
| Table 6. Specifications, continued | 
 | |||||||
| Description | Size 00, 0 | Size 1 | Size 2 | Size 3, 4 | Size 5 | 
| Finger Protection | 
 | 
 | 
 | 
 | 
 | 
| Front | IP20 | IP20 | IP20 | IP20 | IP20 | 
| At Terminals | IP10 | IP10 | IP00 | IP00 | IP00 | 
| At Terminals with max. | IP20 | IP10 | IP10 | IP00 | IP00 | 
| size wire installed | 
 | 
 | 
 | 
 | 
 | 
| Terminals L1, L2, L3/T1, T2, T3 | 
 | 
 | 
 | 
 | 
 | 
| 1 Wire per Terminal | 14 – 8 AWG | 14 – 4 AWG | 14 – 1 AWG | 6 – 250 MCM | 4 – 750 MCM | 
| (stranded or solid) | (1.5 – 10 mm2) | (1.5 – 16 mm2) | (1.5 – 35 mm2) | (16 – 120 mm2) | (25 – 420 mm2) | 
| 2 Wires per Terminal | 14 – 10 AWG | 14 – 6 AWG | 14 – 2 AWG | 6 – 3/0 AWG | 1/0 — 300 MCM | 
| (stranded or solid) | (1.5 – 4 mm2) | (1.5 – 16 mm2) | (1.5 – 25 mm2) | (16 – 70 mm2) | (50 — 150 mm2) | 
| Strip Length | .45" (11 mm) | .5" (12 mm) | .7" (18 mm) | .8" (21 mm) | 1.5" (40 mm) | 
| Torque (max.) | 20  | 35  | 45  | 250  | 550  | 
| 
 | for 14 – 10 AWG | for 14 – 10 AWG | Single 14 – 8 AWG | 
 | 
 | 
| 
 | (1.5 – 6 mm2); | (1.5 – 6 mm2); | (1.5 – 10 mm2); | 
 | 
 | 
| 
 | 25  | 40  | 100  | 
 | 
 | 
| 
 | 8 AWG (10 mm2) | 8 AWG (10 mm2); | Single 6 – 1 AWG | 
 | 
 | 
| 
 | 
 | 45  | (16 – 35 mm2) and | 
 | 
 | 
| 
 | 
 | 6 – 4 AWG | Dual Wire | 
 | 
 | 
| 
 | 
 | (16 mm2) | Combinations | 
 | 
 | 
| Driver | 2.5 mm Hex Key | 3 mm Hex Key | 5/32" (4 mm) Hex Key | 5/16" (8 mm) Hex Key | 5/16" (8 mm) Hex Key | 
| Operation Performance | 
 | 
 | 
 | 
 | 
 | 
| Coil Voltage (nominal) | 24V DC | 24V DC | 24V DC | 24V DC | 24V DC | 
| Coil Operating | 20 – 28 | 20 – 28 | 20 – 28 | 20 – 28 | 20 – 28 | 
| Voltage Range (V DC) | 
 | 
 | 
 | 
 | 
 | 
| Control Terminals | 
 | 
 | 
 | 
 | 
 | 
| (- and +) | 14 – 12 AWG | 14 – 12 AWG | 14 – 12 AWG | 14 – 12 AWG | 14 – 12 AWG | 
| 1 Wire per Terminal | (1.5 – 2.5 mm2) | (1.5 – 2.5 mm2) | (1.5 – 2.5 mm2) | (1.5 – 2.5 mm2) | (1.5 – 2.5 mm2) | 
| (- and +) | 14 AWG | 14 AWG | 14 AWG | 14 AWG | 14 AWG | 
| 2 Wires per Terminal | (1.5 mm2) | (1.5 mm2) | (1.5 mm2) | (1.5 mm2) | (1.5 mm2) | 
| (P, F, R, 1, 2, 3) | 22 – 12 AWG | 22 – 12 AWG | 22 – 12 AWG | 22 – 12 AWG | 22 – 12 AWG | 
| 1 Wire per Terminal | (0.5 – 2.5 mm2) | (0.5 – 2.5 mm2) | (0.5 – 2.5 mm2) | (0.5 – 2.5 mm2) | (0.5 – 2.5 mm2) | 
| (P, F, R, 1, 2, 3) | 18 – 14 AWG | 18 – 14 AWG | 18 – 14 AWG | 18 – 14 AWG | 18 – 14 AWG | 
| 2 Wires per Terminal | (0.75 – 1.5 mm2) | (0.75 – 1.5 mm2) | (0.75 – 1.5 mm2) | (0.75 – 1.5 mm2) | (0.75 – 1.5 mm2) | 
| Torque (max.) | 4.5  | 4.5  | 4.5  | 4.5  | 4.5  | 
| Strip Length | .25 (7 mm) | .25 (7 mm) | .25 (7 mm) | .25 (7 mm) | .25 (7 mm) | 
| Driver | .13 (3.5 mm) Flat | .13 (3.5 mm) Flat | .13 (3.5 mm) Flat | .13 (3.5 mm) Flat | .13 (3.5 mm) Flat | 
| Temperature | 
 | 
 | 
 | 
 | 
 | 
| Operating | |||||
| 
 | |||||
| Storage | |||||
| 
 | |||||
| Environmental | 
 | 
 | 
 | 
 | 
 | 
| Shock/Vibration | 15G/5G | 15G/5G | 15G/5G | 15G/5G | 15G/5G | 
| Altitude | 6600 FT (2000M) | 6600 FT (2000M) | 6600 FT (2000M) | 6600 FT (2000M) | 6600 FT (2000M) | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
| Excl. Debounce Time | 15 | 15 | 25 | 30 | 70 – 200 | 
| Incl. Debounce Time | 75 | 80 | 88 | 95 | 120 – 300 | 
| Dropout Time (mS) @ 24V | 
 | 
 | 
 | 
 | 
 | 
| Excl. Debounce Time | 5 | 5 | 12 | 15 | 50 – 150 | 
| Incl. Debounce Time | 65 | 70 | 75 | 80 | 70 – 250 | 
Use Class B 75°C copper wire only (or 90°C copper wire sized for 75°C operation per NEC).
Consult factory for higher ratings.
The 
Notes:
■Response time for Control Inputs = Debounce Time
■The time between operating forward and reverse must be greater than the Debounce Time.
Note: At other temperatures expressed in °C, for either inrush or sealed, use the 20°C value from the table in the following
Watts = W20 [1.1 
Amps = A20 [1.1 
For example, inrush requirements for a NEMA
Size 2 Starter at 
Table 7. 24V DC Power Supply Requirements @ 68°F (20°C) (see Note at left)
| Contactor/Starter Size | Sealed In | 
 | Inrush | 
 | 
 | |
| Catalog | NEMA Size | Wattage | Amps | Wattage | Amps | Duration | 
| Number | 
 | 
 | 
 | 
 | 
 | (mS) | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| N_11B_ _X3N | 00, 0 | 3.7 | .15 | 80 | 3.3 | 50 | 
| N_01B_ _ _3A | 00, 0 | 3.2 | .13 | 80 | 3.3 | 50 | 
| N_11C_ _X3N | 1 | 4.2 | .18 | 90 | 3.8 | 50 | 
| N_01C_ _ _3A | 1 | 3.6 | .15 | 90 | 3.8 | 50 | 
| N_ _1D_ _ _3_ | 2 | 5.0 | .21 | 130 | 5.4 | 65 | 
| N_ _1E_ _ _3_ | 3, 4 | 5.6 | .23 | 140 | 5.8 | 85 | 
| N_ _1F_ _ _3_ | 5 | 12.0 | .50 | 200 | 8.3 | 250 | 
| N_01F_ _ _3_ | 5 | 13.0 | .54 | 200 | 8.3 | 250 | 
_ indicates missing digit/character of the Catalog Number; may have multiple values.
| CA03310002E | For more information visit:  |