Eaton Electrical CA03310002E Trip Times, Utilization Categories, Category Typical Application

Page 12

12

NEMA Contactors & Starters

IT. Electro-Mechanical

 

September 2003

Technical Data and Specifications

Electrical Life — AC-1, AC-2, AC-3 and AC-4 Utilization Categories

Table 8. Utilization Categories

The International Electrotechnical Commission (IEC) has developed utilization categories for contactors and auxiliary contacts. The IEC utilization categories are used to define the type of electrical load for estimating electrical life, and do not imply the devices are IEC rated.

Category

Typical Application

AC-1

AC-2

AC-3

AC-4

Non-inductive or slightly inductive loads: Resistance furnaces, heating.

Slip-ring motors: Starting and stopping of running motors

Squirrel cage motors: Starting, switching off motors during running (motors in most industrial applications typically fall into this category).

Squirrel cage motors: Starting, plugging , inching (very few applications in industry are totally AC-4).

Plugging is stopping or reversing the motor rapidly by reversing the connections while the motor is running.

Inching or jogging is energizing the motor once or repeatedly for short durations to obtain small movements of the motor driven load.

Life Load Curves — Eaton’s Cutler- Hammer IT. Electro-Mechanical Series NEMA contactors have been designed and manufactured for superior life per- formance. All testing has been based on requirements as found in IEC

60947-4-1 and conducted by us. When selecting a contactor, the specifier must give attention to the specific load, utilization category and the required electrical life. For a definition of Utilization Categories, see Table 8 above.

Note: AC-3 tests are conducted at rated device currents and AC-4 tests are con- ducted at six-times rated device currents. All tests have been run at 460V, 60 Hz.

Actual application life may vary, depending on environmental condi- tions and application duty cycle.

Contactor Choice —

Decide what utilization category the application is and choose the appropriate curve from Figure 1 or Figure 2.

Locate the intersection of the life- load curve with the operational cur- rent (le) of the application, as found on the horizontal axis.

Read the estimated contact life along the vertical axis in number of operations.

Trip Times

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NEMA Size

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10,000,000

 

 

 

00 0

1

 

 

 

2

3 4

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operations

1,000,000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100,000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10,000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

9

 

 

18

27

45

90

135

270

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

100

1000

Note: Preliminary data.

 

 

 

 

 

 

 

 

 

 

Operational Current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 1. Electrical Life — AC-3 Utilization Category

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00 0

1

2

3 4

5

 

NEMA Size

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10,000,000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operations

1,000,000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100,000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10,000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

9

 

 

18

27

45

90

135

270

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

100

1000

Note: Preliminary data.

 

 

 

 

 

 

 

 

 

 

Operational Current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 2. Electrical Life — AC-4 Utilization Category

1000.0

100.0

 

 

 

 

 

 

(Seconds)

10.0

 

5

 

 

 

 

 

 

 

Time

 

 

3

 

 

Trip

 

 

 

 

 

 

6

 

 

1

 

 

 

4

 

1.0

2

 

 

 

 

 

 

0.1

2

3

4

5

6

7

8

9

10

1

Multiples of FLA

1Trip Class 10 Cold

2Trip Class 10 Hot

3Trip Class 20 Cold

4Trip Class 20 Hot

5Trip Class 30 Cold

6Trip Class 30 Hot

Figure 3. Class 10, 20 and 30 Trip Curves

For more information visit: www.cutler-hammer.eaton.com

CA03310002E

Image 12
Contents Contents Nema &ContactorsStartersProduct Description Standards and CertificationsPublications ISO 9002 CertificationCatalog Number Selection Open Components SeptemberIT. Electro-Mechanical Catalog Numbering System ExamplesFeatures ContentsReversing Contactors Product Selection Non-reversing ContactorsFull Voltage 3-Pole DC-Operated Non-reversing Contactors NemaFull Voltage 3-Pole DC-Operated Reversing Contactors N511BSAX3NReversing Starters Starters Non-reversing and ReversingNon-reversing Starters With 3-Pole Solid-State Overload ProtectionN501BSAA3A N501BSAB3AN501BSAC3A N501BSAD3AOverall Dimensions in Inches mm w x h x d Weights in Lb. kgMounting Hole Spacing in Inches mm w x h Mounting PositionsDC Power Supply Requirements @ 68F 20C see Note at left Trip Times Utilization CategoriesCategory Typical Application Modular Components Contactor Field Assembly Modular Components Starter Field AssemblyN04NCS1X3N + N05NCXRL3A = N101CS1L3A Nema Contact Block Nema Solid-State Overload Relay Non-reversingNema Coil Controller Nema Contact Block Nema Solid-State Overload Relay Non-reversingAuxiliary Contacts Tables 18 Nema Snap ConnectivityS751 Snap Connectivity Nema N101, N501 Size Continuous Ampacity RatingDeviceNet Specifications Dsnap SpecificationsProduct Selection Transportation/StorageNon-reversing Contactors Sizes 00 Auxiliary Added w Hole to To Top DIN RailApproximate Dimensions in Inches mm Non-reversing Contactors Sizes 2Non-reversing Contactors Size Reversing Contactors Sizes 00 Reversing Contactors Size Non-reversing Starters Sizes 00 Non-reversing Starter Size Reversing Starters Sizes 00Overall Auxiliary Hole to TopReversing Starter Size