CyberPower Systems CPS3000PIE user manual Fault Warning Display And Alarm, Condition, Solution

Page 12
1.Wait for the backlight to turn off

CPS3000PIE

Step 3: Press and hold the toggle for 4 seconds. When the icons blink, the value of each item can be changed by slightly pressing the toggle.

Step 4: To save the value and return to general mode, press and hold the toggle for 4 seconds.

Note: If the machine is left idle for over 30 seconds during setup, it will turn off the backlight and return to general mode automatically.

Note: If user wants to return to general mode without saving changes, there are two methods:

1.Wait for the backlight to turn off

2.Press and hold the “Display” toggle for 10 seconds

FAULT WARNING DISPLAY AND ALARM

1.Overheat Protection

zEPS overheatThe output of the machine is removed and the LCD display shows the temperature exceeds 70(157). FAULT Icon lights as well.

2.Over-voltage ProtectionThe output of the machine is removed. Over Load and FAULT Icon lights on the LCD display.

3.Battery MissingA long beep is heard and Battery Icon flashes

4.The following table shows each corresponding warning message on the LCD display and the alarm action when the machine output is off

 

 

Condition

Solution

LCD Warning

Alarm

 

 

Display

 

 

 

 

 

 

 

Fault Icon

Rapid Beep

High Temperature

Check fans function and

>70

 

Output-Off

air vent clearances.

 

 

Over 70

 

Over Load Icon.

Long Beep

Over Load Output-Off -

Check total load to

Fault Icon

 

Load exceed the rating of

confirm the rating of EPS.

 

 

EPS.

 

11

Image 12
Contents CPS3000PIE USER MANUAL K01-0000010-00TABLE OF CONTENTS SAFETY AND EMC INSTRUCTIONS………….……………………………………….………1EPS STATUS INQUIRY AND FUNCTIONS SETUP…….……………………………………8 FAULT WARNING DISPLAY AND ALARM……………………………………….………10SAFETY AND EMC INSTRUCTIONS SAVE THESE INSTRUCTIONS K01-0000010-00DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT HARDWARE INSTALLATION GUIDE UNPACKINGAUTOMATIC VOLTAGE REGULATOR INSTALLING YOUR EPSDESCRIPTION 7. Battery Input Wiring Fault LED8. Bypass Switch 9. Power SwitchInstallation Guide 10. Power On Indicator12. LCD Display Toggle / Selected Switch 11. LCD Module DisplayREPLACING THE BATTERY DEFINITIONS FOR ILLUMINATED LCD ELECTRICAL SHOCKEPS Status Inquiry and Functions Setup 1. General Mode2. Set-up Mode ItemsUnit FAULT WARNING DISPLAY AND ALARM SolutionCondition 1. Wait for the backlight to turn offTROUBLESHOOTING ProblemSolution Possible CauseTECHNICAL SPECIFICATIONS External BatteryModel CPS3000PIE