CPS3000PIE
BASIC OPERATION
DESCRIPTION
1. AC Outlets
The unit has two Schuko outlets and one terminal for connected equipment which ensures temporary uninterrupted operation of your equipment during a power failure.
Max. output of 1a is 20A; Max. output of 1b is 15A;
Max. output wattage of (1a+1b) is 2250W
Note:Maximum cord length is 10 meters and the cable O.D. must be 12AWG or greater.
2. AC Inlet
AC input terminals
Note:The O.D. of the distribution cables must be 12AWG or greater.
3.DC Inlet
Battery input terminals
Note:Maximum battery wiring cable length is 2 meters and the cable O.D. must be 2AWG or greater.
4. DC Circuit Breaker
Located on the side of the EPS, the circuit breaker serves to provide overload and fault protection.
5. AC Output Circuit Breaker
Located on the side of the EPS, the circuit breaker serves to provide overload and fault protection. The breaker only works on 1b.
6. AC Input Circuit Breaker
Located on the side of the EPS, the circuit breaker serves to provide overload and fault protection.
7. Battery Input Wiring Fault LED
Battery input wiring fault LED will illuminate to indicate the wiring polarity is reversed.
8. Bypass Switch
Enabling this switch provides the bypass for charge only. UPS will not function if the switch is enabled.
9. Power Switch
Used as the master on/off switch for equipment connected to the battery power supplied outlets.