Spectra Logic T200, T-FINITY, T950, T680 Continuing or Stopping Backups, Ensuring ESD Protection

Page 4

Prepare for Maintenance

PREPARE FOR MAINTENANCE

Make sure you fulfill the prerequisites described in this section and familiarize yourself with all the sections in the document before starting.

Continuing or Stopping Backups

 

Use the following guidelines if you are installing or replacing a drive in a

 

drive bay assembly (DBA) already in the library.

 

 

Method

Description

 

 

QIP-attach drives

Backups running to all other drives in the library (or partition) can safely

(all libraries)

continue while you install a new drive or replace an existing one.

 

 

Direct-attach SCSI

If multiple direct‐attach SCSI drives are daisy‐chained on the same SCSI bus,

drives

adding or removing a drive interrupts communications on the bus. Stop backup

(Spectra T200,

operations to all of the drives in the daisy chain. Spectra Logic recommends

T380, T680)

shutting down and powering off the host computer before replacing a drive.

 

Note: Both the T950 and the T‐Finity require a QIP for direct‐attach drive

 

configurations.

 

 

Direct-attach Fibre

Backups running to other drives in the library (or partition) can safely continue

Channel drives

while you install a new drive or replace an existing one, unless the drive you are

(Spectra T200,

replacing is the one exporting the library (that is, providing the robotic control

T380, T680)

path for the partition). If the drive you are replacing provides the control path

 

for the robotics, stop backup operations to the partition.

 

Note: Both the T950 and the T‐Finity require a QIP for direct‐attach drive

 

configurations.

 

 

Note: Selecting a drive to provide the robotic control path is part of configuring a partition. Refer to the individual User Guide for more information.

Ensuring ESD Protection

The repair environment for the library must be free of conditions that could cause electrostatic discharge (ESD). To protect the library from ESD, follow these procedures:

ƒPlace a static protection mat on the work surface used while removing and installing library components. Use a 1‐megaohm resistor to ground the static protection mat.

ƒWear a static protection wrist band whenever you handle library components that have been removed from their antistatic bags. Connect this wrist band to the static protection mat or to other suitable ESD grounding.

ƒKeep all components in antistatic bags when not in use.

4

Drive Installation or Replacement Instructions

91010010

Image 4
Contents Spectra T200, T380, T680, T950, and T-Finity Copyright Part Number Revision History Drive Installation or Replacement Instructions Prepare for Maintenance Continuing or Stopping BackupsEnsuring ESD Protection Gathering Tools and Supplies Identify the Drive LocationSpectra T200, T380, or T680 Library Back panel drive locations and their identifiers T380 shownSpectra T950 or T-Finity Library Drive Replacement Preparation Replace or Install a DrivePreparing the Library Select Configuration Drives. The Drives screen displays Accessing the Drives Drive Installation PreparationRear panel cover and screws T380 shown Back of the library T950 shown Removing the Malfunctioning Drive Releasing the drive lockInstalling the Drive Releasing the drive lock and removing the driveRemove the drive from its protective packaging Installing the drive sled into the library Complete the Procedure Connecting the CablesDaisy-Chain Direct-Attach Scsi Drives Complete the Procedure May Connect the Scsi Cables Connect the Fibre Channel CablesTesting the Drive Installing the Cover or Securing the Rear DoorAdding the Drive to a Partition Restarting Backups Return ProceduresReturn the Component Return Guidelines