ProtoNode Driver Manual
Page 5 of 17
3.Hardware Connections
The ProtoNode is connected to the UPS as shown in connection drawing. Configure the TIC UPS according to manufacturer’s instructions.
Toshiba UPS
| DB9M | ||||
FUNCTION | FROM | TO | COLOUR | ||
| |||||
Rx | GREY |
| |||
GND | GREEN |
| |||
Tx | BLUE |
|
|
|
|
| ||
FUNCTION | FROM | TO | COLOUR |
|
|
Rx | WHITE |
|
| ||
GND | GREEN |
|
| ||
Tx | BLUE |
|
| ||
|
|
|
|
| |
|
|
|
| PROTONODE |
|
|
|
| DB9F | TOSHIBA UPS |
|
|
|
| CONNECTION DIAGRAM | ||
|
|
|
| ||
| PROTONODE |
| BASE NAME: | DATE: 10/10/07 | |
|
|
|
| FILE NAME: | BY: MC |
3.1.Hardware Connection Tips / Hints
The RTS/DTS signals are not used by the driver. Make sure they are not connected and do not enable them in the configuration file.
The cable must be a NULL modem cable, i.e. the TX must be connected to the other connector’s RX.
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web:www.protocessor.com