FieldServer FS-8700-124 instruction manual Appendix A.1.2. Alarm command, Bit # Description

Page 13

ProtoNode Driver Manual (FS-8700-124) rev 6.doc Manual

Page 13 of 17

Appendix A.1.2. ALARM command:

Stored in bits, make sure array’s length is 24 and its type is bits.

Bit #

Description

Bit 23:

Not used

Bit 22:

1

Bit 21:

Low battery voltage

Bit 20:

Battery replacement alarm

Bit 19:

Parallel running mode

Bit 18:

0

Bit 17:

0

Bit 16:

UPS lifetime alarm

Bit 15:

Not used

Bit 14:

1

Bit 13:

Asynchronous operation

Bit 12:

Ambient overheat

Bit 11:

Overload accumulation started

Bit 10:

0

Bit 9:

0

Bit 8:

0

Bit 7:

Not used

Bit 6:

1

Bit 5:

Countdown started for shutdown

Bit 4:

0

Bit 3:

0

Bit 2:

0

Bit 1:

0

Bit 0:

0

Appendix A.1.3. STATUS command:

Stored in bits, make sure array’s length is 8 and its type is bits.

Bit #

Description

Bit 7:

Not used

Bit 6:

1

Bit 5:

UPS fault detected

Bit 4:

Input voltage out of spec

Bit 3:

Low battery voltage detected

Bit 2:

UPS output from bypass

Bit 1:

UPS output from inverter

Bit 0:

UPS input and output voltage sync

ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web:www.protocessor.com

Tel: 408.964.4433 Fax: 408.964.4425 Toll_Free: 800.317.8319 email: sales@protocessor.com

Image 13
Contents Driver Version Document Revision Effective for all systems manufactured after May 1Table of Contents Max Nodes Supported ProtoNode Mode Comments Required 3rd Party Software Required 3rd Party ConfigurationToshiba UPS Hardware Connection Tips / HintsSection Title Data Arrays/DescriptorsColumn Title Function Legal Values ExampleNone EvenClient Side Node Descriptors Section Title ProtoNode Driver Manual FS-8700-124 rev 6.doc Manual Example Alarm Following commands are supported with the Rdbc function ProtoNode Driver Manual FS-8700-124 rev 6.doc Manual Command DescriptionBit # Function Appendix A.1.1. Fault commandAppendix A.1.3. Status command Appendix A.1.2. Alarm commandBit # Description 1600 1800 4200 G8000 & G8000MM G9000 Appendix A.2. Client Write Commands1600 1800 4200 G8000 & G8000MM, G9000 Appendix A.2.1. Commands supported by different modelsPage ProtoNode Driver Manual FS-8700-124 rev 6.doc Manual Page 17