FieldServer FS-8700-60 Section Title, Column Title Function Legal Values, Example

Page 6

FS-8700-60 Gardner Denver Manual

Page 4 of 11

4.Configuring the FieldServer as a Gardner Denver Auto Sentry ES/RS2000 Client

For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” sample files provided with the FieldServer). This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a Gardner Denver Auto Sentry ES/RS2000 Controller.

1.04Data Arrays/Descriptors

The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for Gardner Denver Auto Sentry ES/RS2000 communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the destination device addresses need to be declared in the “Client Side Nodes” section, and the data required from the servers needs to be mapped in the “Client Side Map Descriptors” section. Details on how to do this can be found below.

Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

 

Section Title

 

 

 

 

Data_Arrays

 

 

 

 

Column Title

Function

 

Legal Values

 

Data_Array_Name

Provide name for Data Array

 

Up to 15 alphanumeric

 

 

characters

 

 

 

 

 

 

Provide data format. Each Data

 

Float, UInt16, Uint32,

 

Data_Array_Format

Array can only take on one

 

Byte, Packed_Byte,

 

 

format.

 

Swapped_Byte

 

 

Number of Data Objects. Must

 

 

 

 

be larger than the data storage

 

 

 

Data_Array_Length

area required by the Map

 

1-10,000

 

 

Descriptors for the data being

 

 

 

 

placed in this array.

 

 

 

Example

 

 

 

 

 

 

 

 

 

// Data Arrays

 

 

 

 

Data_Arrays

 

 

 

 

Data_Array_Name,

Data_Format,

Data_Array_Length,

 

DA_Service_Data,

Uint32,

38

 

DA_Oper_Mode,

UInt16,

3

 

 

DA_Oper_Data,

Uint16,

5

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Image 6
Contents FS-8700-60 Gardner Denver Auto Sentry ES/RS2000 Effective for all systems manufactured after May 1Table of Contents Max Nodes Supported FieldServer Mode Comments FieldServer Technologies Description Required 3rd Party ConfigurationFS-8700-60 Gardner Denver Manual Driver Scope of Supply Required 3rd Party HardwareFS-8700-60 Gardner Denver Manual Hardware Connections Section Title Column Title Function Legal ValuesExample FS-8700-60 Gardner Denver Manual NoneNodes Timing Parameters Column Title Function Legal Values Data will be stored as follows Map Descriptor Example 2 Polling only specific data items Node1 OperatingData MotorcurrentFS-8700-60 Gardner Denver Manual Appendix 1. Advanced Topics JDM