| Page 16 of 51 |
|
|
5.Configuring the FieldServer as a DNP 3.0 Driver Server
For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” files provided with the FieldServer.)
This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a DNP 3.0 Driver Client.
The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for DNP 3.0 Driver communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the FieldServer virtual node(s) needs to be declared in the “Server Side Nodes” section, and the data to be provided to the Clients needs to be mapped in the “Server Side Map Descriptors” section. Details on how to do this can be found below.
Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.
5.1.Server Side Connection Descriptors
| Section Title |
|
|
|
|
|
|
|
| Connections |
|
|
|
|
|
|
|
| Column Title |
|
|
| Function | Legal Values | ||
| Port |
| Specify which port the device is connected to the | |||||
|
|
| FieldServer |
|
|
|
| |
| Baud* |
| Specify baud rate |
|
| 110 – 115200, standard baud | ||
|
|
|
| rates only | ||||
|
|
|
|
|
|
|
| |
| Parity* |
| Specify parity |
|
|
| Even, Odd, None, Mark, Space | |
| Data_Bits* |
| Specify data bits |
|
| 7, 8 | ||
|
|
|
|
|
|
|
|
|
| Stop_Bits* |
| Specify stop bits |
|
| 1 | ||
|
|
|
|
|
|
|
|
|
| Protocol |
| Specify protocol used |
|
| DNP | ||
|
|
|
|
|
|
|
|
|
| Handshaking* |
| Specify hardware handshaking | None | ||||
| Example |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| // Server Side Connections |
|
|
|
| |||
| Connections |
|
|
|
|
|
|
|
| Port | ,Baud | ,Parity | ,Protocol | ,Handshaking |
|
| |
| P8 | ,9600 | ,None | ,DNP | ,None |
|
|
2Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com