FieldServer FS-8700-47 instruction manual Appendix A.7. Internal Indications, Object 80 and Dnpii

Page 28

FS-8700-47 DNP 3.0 Driver Manual

Page 28 of 51

 

 

Appendix A.7. Internal Indications, Object 80 and DNP_II

The driver can store the Internal Indications Bits found in incoming messages and it is possible to control the values of the internal indication bytes sent in responses. In addition, the driver can be configured to respond to the Poll for Object 80 (Internal Indications)

A.7.1. Incoming Internal Indications Bytes

This driver can expose data from the most recently consumed message and additional diagnostic information using a special Map Descriptor called “DNP_ii” (DNP Internal Indications)

The following example shows the configuration of this Map Descriptor. Only one of these Map Descriptors may be configured per FieldServer.

Nodes

 

 

 

Node_Name

,Protocol

 

 

Null_Node

,DNP

 

 

Data_Arrays

 

 

 

Data_Array_Name

,Data_Format

 

,Data_Array_Length

DNP_DIAG

,UINT32

 

,100

Map_Descriptors

 

 

 

Map_Descriptor_Name

,Data_Array_Name,

,Node_Name

dnp-ii

,DNP_DIAG

,

,Null_Node

The following data is stored in the Data Array DNP_DIAG.

Array

 

Contents

 

Element

 

 

 

 

 

 

 

The first byte of the Internal indication reported by a DNP device as found in the most

 

 

recently received message.

 

 

Only messages complete enough to warrant parsing will cause this item to be

0

 

updated.

 

 

 

DNP devices only contain internal indication bytes when the message is an application layer response type message. Typically this includes all responses to data queries/writes as well as unsolicited messages.

1The 2nd byte of the response internal indication.

Bit zero is the least significant bit.

A one (1) in the bit position indicates the described state.

Bit

 

Explanation

 

#

 

 

 

 

 

 

 

First Byte

 

All stations message received

Bit

Set when a request is received with the destination address of the all stations address (ffff

hexadecimal).

0

Cleared after next response (even if response to global request is required)

 

 

Used to let the master station know that a Broadcasted message was received by this station.

Bit

Class 1 data available

Set when data that has been configured as Class 1 data is ready to be sent to the master

1

Master station should request this class data from the Outstation when this bit is set in a

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com

Image 28
Contents Driver Manual FS-8700-47 DNP Table of Contents FS-8700-47 DNP 3.0 Driver Manual Table of Contents DNP 3.0 Driver Description Page FS-8700-47 DNP 3.0 Driver Manual Hardware Connections Connection NotesConfiguring the FieldServer as a DNP 3.0 Driver Client Data ArraysClient Side Connection Descriptors Client Side Node DescriptorsDriver Specific Map Descriptor Parameters Timing Parameters Map Descriptor Example 1 Simple Read Map Descriptor Example 3 Simple Read Extract Value & Status Map Descriptor Example 4 Reading Class Data Map Descriptor Example 6 Read an unknown variation Configuring the FieldServer as a DNP 3.0 Driver Server Server Side Connection DescriptorsServer Side Node Descriptors Driver Specific Map Descriptor Parameters Map Descriptor Example 1 Discrete Data Map Descriptor Example 2 Class DataMap Descriptor Example 3 Class Data another example RTUMap Descriptor Example 4 Default Variation Variation zero Map Descriptor Example 5 ClassDataServingCtrl AnaInputs Map Descriptor Example 6 Unsolicited Messages Server Side Limitations Appendix A. Advanced Topics Appendix A.1. DNP 3.0 Protocol Appendix A.2. DNP Driver FunctionalityAppendix A.3. DNP Objects mapped to FieldServer Data Arrays Appendix A.4. Channel Idle, Master & Slave IdleAppendix A.5. DLL Layer Functionality in the Master Appendix A.6. App Layer Functionality in the MasterAppendix A.7. Internal Indications, Object 80 and Dnpii Incoming Internal Indications BytesPage Internal Indications reported in Responses ServerIIArrayResponses to Polls for Object 80 Internal Indications Appendix A.8. DNPStats DnpstatsAppendix A.9. DNP 3.0 Data Objects Counter Change Event All Variations See notes in Appendix A.10 for function code FS-8700-47 DNP 3.0 Driver Manual Appendix A.11. Controlling the DNP 3.0 Driver’s Qualifier Appendix A.12. FieldServer DNP Node NumberAppendix A.13. DnpSubType Appendix A.15. Link ResetAppendix A.14. Communication Stats Appendix A.16. Controlling DA Offsets Appendix A.17. dnpIndexStyleAppendix A.18. Real Time Clock Synchronization DatimePage Appendix A.19. Select and Operate Page Page Appendix A.20. Multiple requests in a single poll Appendix B. Driver Error Messages Page Page Page FYI