FieldServer HCS-R, FS-8700-127 Appendix A.1.1 DataType is AnaInput or not specified

Page 15

FS-8700-127 Hanning & Kahl HCS-R Manual

Page 15 of 17

Appendix A. Advanced Topics

Appendix A.1. 1. How Client Stores Data:

The HCS will be polled by an RDBC Map Descriptor and data will be stored in the DA_Current Data Array in the following fashion if parameter HCSR_Data_Stages >1:

New data is stored as current data.

If data is changed, last current data is moved to 2nd Stage, 2nd Stage data is moved to 3rd stage and 3rd stage data is lost.

Appendix A.1.1.

Data_Type is Ana_Input or not specified

 

 

 

 

 

 

 

 

 

Data Array Offset

 

 

 

Description

 

 

 

Current Data

 

 

 

 

 

 

 

 

0 - 18

 

Data bits ( 0 - 1 )

 

 

 

19

 

Receipt ok ( 0 ), Disturbance ( 1 )

 

 

 

20

 

From Loop ( 0 ), On Loop ( 1 )

 

 

 

21

 

Loop Number (1,2,3,4) as integer

 

 

 

2nd (Previous) Data

 

 

 

 

 

 

 

 

24 – 42

 

Data bits ( 0 – 1 )

 

 

 

43

 

Receipt ok ( 0 ), Disturbance ( 1 )

 

 

 

44

 

From Loop ( 0 ), On Loop ( 1 )

 

 

 

45

 

Loop Number (1,2,3,4) as integer

 

 

 

3rd (Prior to previous) Data

 

 

 

 

 

 

 

48 – 66

 

Data bits ( 0 – 1 )

 

 

 

67

 

Receipt ok ( 0 ), Disturbance ( 1 )

 

 

 

68

 

From Loop ( 0 ), On Loop ( 1 )

 

 

 

69

 

Loop Number (1,2,3,4) as integer

 

 

Appendix A.1.2.

Data_Type is Digi_Input

 

 

 

 

 

 

 

 

Data Array Offset (Say 0)

 

 

 

Description

 

 

Current Data

 

 

 

 

 

 

 

 

0 - 18

 

Data bits ( 0 - 1 )

 

 

19

 

Receipt ok ( 0 ), Disturbance ( 1 )

 

 

20

 

From Loop ( 0 ), On Loop ( 1 )

 

 

21,22,23

 

3 bits for Loop Number

 

 

 

 

Offsets

 

 

 

 

 

 

 

21 22 23

 

 

 

 

 

 

1

0

0

–Loop 1

 

 

 

 

0

1

0

–Loop 2

 

 

 

 

1

1

0

–Loop 3

 

 

 

 

0

0

1

–Loop 4

 

 

2nd (Previous) Data

 

 

 

 

 

 

 

 

24 – 42

 

Data bits ( 0 – 1 )

 

 

43

 

Receipt ok ( 0 ), Disturbance ( 1 )

 

 

44

 

From Loop ( 0 ), On Loop ( 1 )

 

 

45

 

Loop Number (1,2,3,4) in 3 bits as above

 

 

3rd (Prior to previous) Data

 

 

 

 

 

 

 

48 – 66

 

Data bits ( 0 – 1 )

 

 

67

 

Receipt ok ( 0 ), Disturbance ( 1 )

 

 

68

 

From Loop ( 0 ), On Loop ( 1 )

 

 

69

 

Loop Number (1,2,3,4) in 3 bits as above

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com Tel: 408 262-2299 Fax: 408-262-2269 Toll_Free: 888-509-1970 email: support@FieldServer.com

Image 15
Contents HCS-R Table of Contents Hanning & Kahl HCS-R Description FS-8700-127 Hanning & Kahl HCS-R Manual Hardware Connection Tips / Hints Hardware ConnectionsConfiguring the FieldServer as a HCS-R Client Data Arrays/DescriptorsDacurrent Hcsr HCS-R Client Side Connection DescriptionsClient Side Node Descriptors HCS-RTiming Parameters Driver Related Map Descriptor ParametersCMDDIHCSR01 Dacurrent Rdbc Map Descriptor Example Read DataCMDDIHCSR01 Dacurrent Rdbc Map Descriptor Example Read Data and Keep HistoryConfiguring the FieldServer as a HCS-R Server Server Side Connection DescriptorsHcsr Server Side Node Descriptors Driver Specific Map Descriptor Parameters SMDHCSR01 Dahcsr Appendix A.1.2 DataType is DigiInput Appendix A.1.1 DataType is AnaInput or not specifiedAppendix A.2 . How Server expects Data Appendix A.2.1 DataType is AnaInput or not specifiedAppendix A.2.2 DataType is DigiInput This page Intentionally Left Blank