FieldServer FS-8700-127, HCS-R instruction manual Appendix A.2 . How Server expects Data

Page 16

FS-8700-127 Hanning & Kahl HCS-R Manual

Page 16 of 17

The same data will be stored in a Loop based Data Array which will then have the last known data for each loop

Data Array Offset

Description

Current Data

 

0 - 18

Data bits ( 0 – 1)

19

Receipt ok ( 0 ), Disturbance ( 1 )

20

From Loop ( 0 ), On Loop ( 1 )

2nd (Previous) Data

 

21 – 39

Data bits ( 0 – 1)

40

Receipt ok ( 0 ), Disturbance ( 1 )

41

From Loop ( 0 ), On Loop ( 1 )

3rd (Prior to previous) Data

 

42 – 60

Data bits ( 0 – 1)

61

Receipt ok ( 0 ), Disturbance ( 1 )

62

From Loop ( 0 ), On Loop ( 1 )

Appendix A.2. 2. How Server expects Data:

The Server expects data in the following format in order to constitute its response to HCS-R Clients.

Appendix A.2.1.

Data_Type is Ana_Input or not specified

 

 

 

 

 

Data Array Offset

Description

 

0 - 18

Data bits ( 0 - 1 )

19Receipt ok ( 0 ), Disturbance ( 1 )

20From Loop ( 0 ), On Loop ( 1 )

21Loop Number (0,1,2,3)

Appendix A.2.2.

Data_Type is Digi_Input

 

 

 

 

 

 

Data Array Offset (say 0)

 

 

Description

 

0 - 18

 

Data bits ( 0 - 1 )

 

19

 

Receipt ok ( 0 ), Disturbance ( 1 )

 

20

 

From Loop ( 0 ), On Loop ( 1 )

 

 

 

2 bits for Loop Number

 

 

 

Offsets

 

 

 

 

21 22

 

 

21,22

 

0

0

–Loop 1

 

 

 

1

0

–Loop 2

 

 

 

0

1

–Loop 3

 

 

 

1

1

–Loop 4

.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com Tel: 408 262-2299 Fax: 408-262-2269 Toll_Free: 888-509-1970 email: support@FieldServer.com

Image 16
Contents HCS-R Table of Contents Hanning & Kahl HCS-R Description FS-8700-127 Hanning & Kahl HCS-R Manual Hardware Connections Hardware Connection Tips / HintsData Arrays/Descriptors Configuring the FieldServer as a HCS-R ClientDacurrent Client Side Connection Descriptions Client Side Node DescriptorsHCS-R Hcsr HCS-RDriver Related Map Descriptor Parameters Timing ParametersMap Descriptor Example Read Data CMDDIHCSR01 Dacurrent RdbcMap Descriptor Example Read Data and Keep History CMDDIHCSR01 Dacurrent RdbcServer Side Connection Descriptors Configuring the FieldServer as a HCS-R ServerHcsr Server Side Node Descriptors Driver Specific Map Descriptor Parameters SMDHCSR01 Dahcsr Appendix A.1.1 DataType is AnaInput or not specified Appendix A.1.2 DataType is DigiInputAppendix A.2.1 DataType is AnaInput or not specified Appendix A.2 . How Server expects DataAppendix A.2.2 DataType is DigiInput This page Intentionally Left Blank