FieldServer Configuring the FieldServer as a HCS-R Server, Server Side Connection Descriptors

Page 11

FS-8700-127 Hanning & Kahl HCS-R Manual

Page 11 of 17

5.Configuring the FieldServer as a HCS-R Server

For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” sample files provided with the FieldServer).

This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a Hanning & Kahl HCS-R Client.

The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for HCS-R communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the FieldServer virtual Node(s) needs to be declared in the “Server Side Nodes” section, and the data to be provided to the clients needs to be mapped in the “Server Side Map Descriptors” section. Details on how to do this can be found below.

Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

5.1.Server Side Connection Descriptors

 

Section Title

 

 

 

 

 

Connections

 

 

 

 

 

 

Column Title

 

Function

 

 

Legal Values

Port

 

 

Specify which port the device is

P1-P83

 

 

 

connected to the FieldServer

 

 

 

 

 

 

 

 

HCS-R

Protocol

 

Specify protocol used

 

HCSR

 

 

 

 

 

H&K HCS-R

Baud*

 

Specify baud rate

 

9600 (Vendor Limitation)

Parity*

 

Specify parity

 

None (Vendor Limitation)

Data_Bits*

 

Specify data bits

 

8 (Vendor Limitation)

 

 

 

 

 

 

 

Stop_Bits*

 

Specify stop bits

 

1

 

 

 

 

 

 

 

 

Handshaking*

 

Specify hardware handshaking

 

None (Vendor Limitation)

 

 

 

Specifies the time that the FieldServer

 

 

 

 

 

will reserve the Server side connection

 

 

Server_Hold_Timeout*

 

while waiting for the Client side to

>1.0s, 2.0s

 

 

 

update data in Data_Array (if

 

 

 

 

 

necessary)

 

 

 

Example

 

 

 

 

 

 

 

 

 

 

//

Server Side Connections

 

 

 

Connections

 

 

 

 

Port,

Protocol,

Baud,

Parity,

 

Handshaking

P8,

HCS-R,

9600,

None,

 

None

3Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com Tel: 408 262-2299 Fax: 408-262-2269 Toll_Free: 888-509-1970 email: support@FieldServer.com

Image 11
Contents HCS-R Table of Contents Hanning & Kahl HCS-R Description FS-8700-127 Hanning & Kahl HCS-R Manual Hardware Connection Tips / Hints Hardware ConnectionsDacurrent Configuring the FieldServer as a HCS-R ClientData Arrays/Descriptors Hcsr HCS-R Client Side Connection DescriptionsClient Side Node Descriptors HCS-RTiming Parameters Driver Related Map Descriptor ParametersCMDDIHCSR01 Dacurrent Rdbc Map Descriptor Example Read DataCMDDIHCSR01 Dacurrent Rdbc Map Descriptor Example Read Data and Keep HistoryHcsr Configuring the FieldServer as a HCS-R ServerServer Side Connection Descriptors Server Side Node Descriptors Driver Specific Map Descriptor Parameters SMDHCSR01 Dahcsr Appendix A.1.2 DataType is DigiInput Appendix A.1.1 DataType is AnaInput or not specifiedAppendix A.2.2 DataType is DigiInput Appendix A.2 . How Server expects DataAppendix A.2.1 DataType is AnaInput or not specified This page Intentionally Left Blank