Page 14

FS-8700-132 Gamewell FCI-E3 Driver Manual

Page 14 of 20

 

 

Appendix A.2. Extending the Event Table

New event causes may be added to the Event Table and the index value or category of existing event causes modified by adding a section to the configuration CSV file. The examples below illustrate this:

Example 1: Index value of 'Trouble' is updated to a new value of 100

Driver_Table

 

 

 

Event_Type_Description,

Event_Type_Index_Value,

Event_Type_Category ,

Protocol

TROUBLE,

 

100,

4,

FCI_E3

Example 2:

New Entry is added

 

 

Since it has been added as category=3, only Map Descriptors with 'Event Type' set to “Alarm” or “Any” will capture messages with this event description

Driver_Table

 

 

 

Event_Type_Description,

Event_Type_Index_Value,

Event_Type_Category,

Protocol

DESTROYED,

51,

3,

FCI_E3

For categories use the following values 'Other' = 1

'Fault' = 2 'Alarm' = 3 'Trouble' = 4

Appendix A.3. How Data is stored

All messages shorter than 102 characters are discarded unless they contain information identifying the networked/local panel. All other messages are processed as follows:

The driver determines if the message is a Zone, Relay, Loop, Sensor, Module or Panel message.

The driver finds all Map Descriptors with matching ‘Point Type’ parameters.

The event category is determined.

Map Descriptor selection is refined based on whether the ‘Event Type’ matches or has been defined as “Any”

The driver determines the Loop. Relay, Zone, Sensor and Module numbers from the message and refines its selection of Map Descriptors by selecting those that match the values determined from the message.

The selected Map Descriptors are now used to determine a Data Array and offset at which to store the data.

Finally the driver checks the ‘Store As’ parameter. If it hasn’t been specified then ‘Index Value’ storage is assumed. If it has been specified as ‘Bits’ then the driver will perform ‘Bit Storage’. In cases where the Map Descriptor has both a primary and secondary Data Array, the driver will use ‘Index Value’ storage using the primary data array and ‘Bit Storage’ using the secondary array.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com

Image 14
Contents Driver Manual FS-8700-132 Gamewell FCI E3 Series Serial Effective for all systems manufactured after SeptemberTable of Contents Gamewell FCI-E3 Series Serial Driver Description Max Nodes SupportedILI-MB-E3 Board GND TB6FCI-E3 Data Arrays/Descriptors FCIE3 Client Side Node Descriptors Driver Related Map Descriptor Parameters First Alarm UP Stairs N. ENT Manual Station L1M21 003728 01/01/99CRLF Darelay FS-8700-132 Gamewell FCI-E3 Driver Manual FS-8700-132 Gamewell FCI-E3 Driver ManualPage 13 Trouble Destroyed FCIE3Damodu ANY Appendix A.4. Panel Synchronization Appendix A.5.1 Networked PanelsFYI Page Appendix B.1. Driver Stats Exposed FCIE3STATNOPLACETOSTORENODE FCIE3STATPARSEDNOERRSEXCLDRESETFCIE3STATRCVDMSGS