4.2.Client Side Connection Descriptions
| Section Title |
|
|
|
|
|
| Connections |
|
|
|
|
|
| Column Title |
| Function |
| Legal Values | |
| Port |
| Specify which port the device is connected to the FieldServer |
| ||
| Protocol |
| Specify protocol used |
| FCI_E3 | |
|
|
| Specify baud rate |
|
|
|
|
|
| Vendor documentation indicated that the only supported Baud | 9600, | 57600 | |
| Baud* |
| rate was 9600. During testing we learned this was not true. The |
| (Vendor | |
|
|
| driver was tested at 57600 and 9600 baud. Testing at 115200 |
| Limitation) | |
|
|
| Baud produced intermittent result and should not be used. |
|
|
|
|
|
|
|
| None | – |
| Parity* |
| Specify parity |
| (Vendor | |
|
|
|
|
| Limitation) | |
| Data_Bits* |
| Specify data bits | 8 | (Vendor | |
|
|
| Limitation) | |||
|
|
|
|
| ||
| Stop_Bits* |
| Specify stop bits | 1 | (Vendor | |
|
|
| Limitation) | |||
|
|
|
|
| ||
| Handshaking* |
| The E3 series panels do not support hand shaking. |
|
|
|
Example
//Client Side Connections
| Connections |
|
|
|
|
| Port, | Protocol, | Baud, | Parity |
|
| P1, | FCI_E3, | 9600, | None |
|
|
|
|
|
|
|
1Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.