FieldServer FS-8700-132, FCI E3 Series instruction manual Client Side Node Descriptors

Page 8

FS-8700-132 Gamewell FCI-E3 Driver Manual

Page 8 of 20

 

 

4.3.Client Side Node Descriptors

 

Section Title

 

 

 

 

 

 

 

 

 

Nodes

 

 

 

 

 

 

 

 

 

Column Title

 

 

Function

 

 

Legal Values

 

 

Node_Name

 

Provide name for Node

 

 

Up to 32 alphanumeric

 

 

 

 

 

characters

 

 

 

 

 

 

 

 

 

 

 

 

 

Only

required

for

networked

 

 

 

 

 

 

configurations. Set the Node_ID of the

 

 

 

 

Node_ID

 

local panel to zero, and create one Node

 

Whole numbers 0,1,2,3 …

 

 

 

 

Descriptor for each panel setting the

 

 

 

 

 

 

Node_ID to the panel number.

 

 

 

 

 

Protocol

 

Specify protocol used

 

 

FCI_E3

 

 

 

 

Only required for networked

 

 

 

 

 

 

 

configurations:

 

 

 

 

 

 

 

 

When not specified or set to

 

 

 

 

 

 

 

‘Reset_by_any_Node ‘ then the driver

 

 

 

 

 

 

will reset the data array points

 

 

 

 

 

FCI_Reset_Action_Option*

 

associated with the given node

 

Reset_by_any_Node,

 

 

 

 

irrespective of the reset message’s

 

Reset_by_this_Node_Only

 

 

 

 

origin.

 

 

 

 

 

 

 

 

 

When set to ‘Reset_by_this_Node_Only’

 

 

 

 

 

 

then the driver only resets the data

 

 

 

 

 

 

associated with the given node if the

 

 

 

 

 

 

reset originated from the same node.

 

 

 

 

Connection

 

Specify which port the device is

 

P1-P82

 

 

 

 

connected to the FieldServer

 

 

 

 

 

Example

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

// Client Side Nodes

 

 

 

 

 

 

 

 

 

Nodes

 

 

 

 

 

 

 

 

 

Node_Name,

Protocol,

 

Connection

 

 

 

 

Panel-01,

FCI_E3,

 

P8

 

 

 

 

4.4.Client Side Map Descriptors

4.4.1.FieldServer Related Map Descriptor Parameters

Column Title

 

Function

 

 

Legal Values

Map_Descriptor_Name

Name

of

this

Map

Up

to 32

alphanumeric

Descriptor

 

 

characters

 

 

 

 

 

 

Name

of

Data

Array

One of the Data Array names

Data_Array_Name

where data is to be stored

from “Data Array” section above

 

in the FieldServer

 

 

 

 

Data_Array_Offset

Starting

location in

Data

0 to

maximum

specified in

Array

 

 

 

“Data Array” section above

 

 

 

 

Function

Function of

Client

Map

Server, Passive_Client

 

Descriptor.

 

 

 

 

 

2Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com

Image 8
Contents Driver Manual FS-8700-132 Gamewell FCI E3 Series Serial Effective for all systems manufactured after SeptemberTable of Contents Gamewell FCI-E3 Series Serial Driver Description Max Nodes SupportedILI-MB-E3 Board GND TB6FCI-E3 Data Arrays/Descriptors FCIE3 Client Side Node Descriptors Driver Related Map Descriptor Parameters First Alarm UP Stairs N. ENT Manual Station L1M21 003728 01/01/99CRLFDarelay FS-8700-132 Gamewell FCI-E3 Driver Manual FS-8700-132 Gamewell FCI-E3 Driver ManualPage 13 Trouble Destroyed FCIE3Damodu ANY Appendix A.4. Panel Synchronization Appendix A.5.1 Networked PanelsFYI Page Appendix B.1. Driver Stats Exposed FCIE3STATNOPLACETOSTORENODE FCIE3STATPARSEDNOERRSEXCLDRESETFCIE3STATRCVDMSGS