Page 18 of 20 |
| ||
|
|
|
|
|
|
|
|
| Message | Description |
|
|
| This message should only be printed if a |
|
| FCI_E3:#17 Err. Loop=%d < 1. Rejected. , | byte in a message has been corrupted. If |
|
| you notice it more than once then take a |
| |
|
|
| |
|
| log and contact tech support. |
|
|
| If this error is repeated often it is possible |
|
| FCI_E3:#18 Err. Loop Type='%c'(%#x) Not recognized. , | that a FCI firmware update has made the |
|
| driver unusable. Take a log and contact |
| |
|
| tech support. |
|
| FCI_E3:#19 Err. Relay=%d < 1. Rejected. , | This message should only be printed if a |
|
| byte in a message has been corrupted. If |
| |
|
|
| |
| FCI_E3:#20 Err. Zone=%d < 1. Rejected. , | you notice it more than once then take a |
|
| log and contact tech support. |
| |
|
|
| |
| FCI_E3:#21 Err. Point Type not recognized | Valid Point Types are listed in section |
|
| FCI_E3:#22 Err. Undefined Point Type" | 4.4.25 |
|
| FCI_E3:#23 Err. Event Type not recognized | Valid Event Types are listed in section |
|
| FCI_E3:#24 Err. Undefined Event Type | 4.4.25 |
|
| FCI_E3:#25a Err. Address+Length>99. Length Truncated | The maximum value for a sensor/module |
|
| FCI_E3:#25b Err. Address+Length>99. Length Truncated | is 99. The combination of address and |
|
| length specified produce a number > 995 |
| |
| FCI_E3:#26 Err. Invalid Module number. Expected 1..99 |
|
|
| FCI_E3:#27a Err. Invalid Loop number. Expected 1..10 |
|
|
| FCI_E3:#27b Err. Invalid Loop number. Expected 1..10 |
|
|
| FCI_E3:#27c Err. Invalid Loop number. Expected 1..10 | Correct the configuration file5 |
|
| FCI_E3:#28 Err. Invalid Sensor number. Expected 1..99 |
|
|
| FCI_E3:#29 Err. Invalid Zone number. Expected 1..255 |
|
|
| FCI_E3:#30 Err. Invalid Relay number. Expected 1..255 |
|
|
| FCI_E3:#31 Err. Point Type Invalid. | Valid Point Types are listed in Section |
|
| 4.4.25 |
| |
| FCI_E3:#32 Err. No MD Length. Default to 1 | The length of each Map Descriptor should |
|
| be specified. Refer to Section 4.4.25 |
| |
|
| The driver can only listen passively for |
|
| FCI_E3:#33 Err. Driver can’t poll or write. | message from the panel. Map Descriptors |
|
|
| may not be configured as active. 5 |
|
|
| An event message is less than 80 bytes |
|
|
| long. If this error is repeated often it is |
|
| FCI_E3:#36 Err. Too Short. Bytes=%d , | possible that a FCI firmware update has |
|
|
| made the driver unusable. Take a log and |
|
|
| contact tech support. |
|
5Correct the configuration file, download to the FieldServer and restart the FieldServer for the changes to take effect.