*Note the following when wiring:

(2) Run/stop command terminal (FWD, REV)

FWD terminal is short-circuit to CM terminal in the factory. Pressing the RUN key on the keypad panel can start forward operation. If function F02 is 0, short-circuit FWD and CM and press the RUN key for forward operation, or short-circuit REV and CM for reverse operation. If function F02 is 1, then short-circuit FWD and CM for forward operation, or REV and CM for reverse operation. Regardless of whether function F02 is set to 0 or 1, short-circuiting both FWD CM and REV CM brings the drive to a deceleration-stop. Refer to F02 “Operation method” for details.

(3) Analog input terminal (13, 12, 11, C1)

Use these terminals to connect external input analog voltage and analog current and frequency setting device (POT). For connecting a contact to this circuit, use a twin contact for fine current sig- nal. Do not use a contact for terminal 11.

!WARNING

1.The STOP key is valid only when the function has been set. Prepare an- other switch for emergency stop. When the data of F02 is selecte “2” or “4”, the operation cannot be stopped using the STOP key on the keypad panel, otherwise accidents could occur.

*Note the following when wiring:

(1) Surge absorber connection

When the exciting coil of the magnetic contactor or relay in the control circuit or drive peripheral circuit is opened or closed, a surge voltage (noise) is generated with a sudden current change. Due to this surge voltage, the drive control circuit or peripheral equipment may malfunction. If so, directly connect a surge absorber to both ends of the coil. (See Fig- ure 2-3-4).)

(2)Control circuit wiring

1 Wires connected to control circuit terminals must be AWG 20 (0.5mm2) shielded wire or twisted vinyl wire. Remove the sheath as shown in Figure 2-3-5 and then connect it.

2Keep the wiring of the main circuit, external relay se- quence circuit and control circuit as far away from each

AC relay

DC relay

 

 

 

 

 

 

 

 

SK

 

 

 

 

 

 

 

 

MC

 

 

 

 

 

+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ry

 

 

 

D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SK: Surge absorber

D: Diode

 

Figure 2-3-4 Surge absorber connection diagram

0.24” ± 0.04” (6±1mm)

other as possible. If they must be adjacent, cross them at right angles.

3Use a twisted-pair shielded wire for long wiring distances.

(3)Shielding sheath connection

Connect one end of the shielding sheath of a shielded or twisted-pair shielded wire to the ground terminal as shown in Figure 2-3-6. Do not connect the other end.

Figure 2-3-5 End treatment

Contact

Shielded wire

 

FWD

 

CM

 

To ground terminal

Frequency

Shielded wire

setting POT

 

 

13

 

12

 

11

 

To ground terminal

Figure 2.3.6 Connection of sheath of shielded wire

-19-