Change during operation: N = impossible, Y* = possible (enabled by using

FUNC DATA

), Y= possible (enabled by using )

F02 Operation method

The following four values can be selected: 0 Keypad operation [ RUN STOP key]

Factory

Change during

setting

operation

0

N

The motor runs when the

RUN

key is pressed and decelerates-to-stop when the

STOP

key is

pressed. The rotation direction depends on the FWD and REV terminals as follows: FWD - CM short-circuited: Forward

REV - CM short-circuited: Reverse

Operation is impossible when both the FWD and REV terminals or none of them are short-circuited with the CM terminal.

1

External signal (Digital input) (FWD, REV)

Forward operation with FWD-CM short-circuited and deceleration to stop with them open Reverse operation with REV-CM short-circuited and deceleration to stop with them open No operation with both FWD-CM and REV - CM short-circuited

STOP key active (See following page chart for detail)

2 External signal (Digital input) (FWD, REV)

Forward operation with FWD-CM short-circuited and deceleration to stop with them open Reverse operation with REV-CM short-circuited and deceleration to stop with them open No operation with both FWD-CM and REV - CM short-circuited

STOP key inactive (See following page chart for detail)

3 External signal (Digital input) (FWD, REV)

Forward operation with FWD-CM short-circuited and deceleration to stop with them open Reverse operation with REV-CM short-circuited and deceleration to stop with them open No operation with both FWD-CM and REV - CM short-circuited

STOP

key active with GE start software (See following page chart for detail)

4

External signal (Digital input) (FWD, REV)

Forward operation with FWD-CM short-circuited and deceleration to stop with them open Reverse operation with REV-CM short-circuited and deceleration to stop with them open No operation with both FWD-CM and REV - CM short-circuited

STOP key inactive with GE start software (See following page chart for detail)

Note: This function can be changed only while the FWD and REV terminals are open.

-39-

Page 41
Image 41
GE C11, AF-300 manual F02 Operation method, Motor runs when, Key is pressed and decelerates-to-stop when