GE AF-300, C11 manual Use MCCB or MC that conforms to EN or IEC standard

Models: C11 AF-300

1 98
Download 98 pages 7.53 Kb
Page 4
Image 4
4.Use MCCB or MC that conforms to EN or IEC standard.

Compliance with low voltage directive in EU [Applicable to products with TÜV mark]

!CAUTION

1.Safe separation for control interface of this drive is provided when this drive is installed in overvoltage category II. PELV(Protective Extra Low Voltage) circuit or SELV(Safety Extra Low Voltage) circuit from external controller is connected to the interface directly.

2.Basic insulation for control interface of this drive is provided when this drive is installed in overvoltage category III. An isolation transformer has to be installed between power supply mains and this drive when SELV circuit from external controller is connected to this drive directly. Otherwise supplementary insulation between control interface of this drive and environment must be provided.

3.The ground terminal Manual backgroundG should always be connected to the ground. Don't use only RCD as the sole method of electric shock protection.

Dimensions of external PE conductor should be same as dimensions of input phase conductor and capable for possible fault.

4.Use MCCB or MC that conforms to EN or IEC standard.

5.Where RCD (Residual-current-operated protective device) is used for protection in case of direct or indirect contact, only RCD of type B is allowed on the supply side of this EE (Electric equipment). Otherwise another protective measure shall be applied such as separation of the EE from the environment by double or reinforced insulation or isolation of EE and supply system by the transformer.

6.The drive has to be installed in environment of pollution degree 2. If the environment is pollution degree 3 or 4, the drive has to be installed in a cabinet of IP54 or higher.

7.Use a prescribed wire according to the EN60204 Appendix C.

8.Install the drive, AC or DC reactor, output filter in an enclosure that meets the following requirement, to prevent a human body from touching directly to these equipment.

1)When a person can touch easily on each connecting terminal or live parts, install the drive, AC or DC reactor, output filter in an enclosure with minimum degree of protection of IP4X.

2)When a person can not touch easily on each connecting terminal or live parts, in- stall the drive, AC or DC reactor, output filter in an enclosure with a minimum de- gree of protection of IP2X.

9.It is necessary to install the drive in appropriate method using an appropriate RFI filter to conform to the EMC directive. It is customer's responsibility to check whether the equip- ment ,the drive is installed in, conforms to EMC directive.

-2-

Page 4
Image 4
GE AF-300, C11 manual Use MCCB or MC that conforms to EN or IEC standard