Image 74

 

Check part

Check item

How to inspect

Evaluation criteria

 

 

Resistor

1)Unpleasant smell and crazing

1)Olfactory and

1)Not abnormal.

 

 

 

of the insulation by

visual inspection

2)Less than about ±10% of

 

 

 

overheating

2)Visual inspection

the indicated

 

 

 

2)No open circuit?

or use a multimeter

resistance value

circuit

 

 

 

by removing a

 

 

 

 

connection on one

 

 

 

 

 

 

Main

 

 

 

side.

 

 

Trans-

Abnormal buzzing or unpleasant

Aural, olfactory, and

Not abnormal.

 

 

 

 

former and

smell?

visual inspection

 

 

 

reactor

 

 

 

 

 

Magnetic

1)Rattling when operating?

1)Aural

1), 2) Not abnormal.

 

 

contactor

2)Roughness of contact?

2)Visual inspection

 

 

 

and relay

 

 

 

 

 

Control PC

1)Loose screws or connectors?

1)Tighten more.

1), 2), 3), 4)

 

 

board and

2)Unpleasant smell or

2)Olfactory and

Not abnormal.

circuit

 

connector

discoloration?

visual inspection

 

 

 

3)Cracks, damage, deformation, or

3),4)Visual

 

 

 

 

 

Control

 

 

excessive rust?

inspection

 

 

 

4)Electrolyte leakage or a

 

 

 

 

 

 

 

 

 

 

deformed mark on the

 

 

 

 

 

capacitor?

 

 

 

 

 

 

 

 

 

 

Cooling

1)Abnormal sound or vibration?

1)Aural and visual in-

1)The fan must rotate

 

 

fan

2)Loose of bolts?

spection. Turn with

smoothly.

 

 

(2 HP or

3)Discoloration by

hand. (Make sure power

2), 3)Not abnormal

system

 

more)

overheating?

is off)

 

 

 

 

2)Tighten more

 

 

 

 

 

 

 

 

 

 

3)Visual inspection

 

Cooling

 

Ventilation

Clogging-up or foreign substance on

Visual inspection

Not abnormal

 

way

heat sink or intake/exhaust ports?

 

 

 

 

 

 

 

 

 

 

 

 

(Note) Use a capacitance measuring instrument available on the market which is easy to use. (Remark) If the equipment is stained, wipe it with a cleaning cloth, which is chemically neutral. Vacuum-clean the dust.