Change during operation: N = impossible, Y* = possible (enabled by using FUNCDATA
), Y= possible (enabled by using )
F20 DC injection brake
(starting frequency)
Factory | Change during |
setting | operation |
| |
3.0Hz | N |
This function sets 3.0Hz (fixed) as the starting frequency of DC injection brake.
F21 | DC injection brake (Braking level) |
Factory | Change during |
setting | operation |
|
|
0% | Y |
This function sets a DC brake current level.
Levels can be set in 1% unit by assuming the level of the drive rated current to be 100%.
F22 DC injection brake(Braking time)
This function sets the DC injection braking time.
0.0: No DC injection braking
0.1to 30.0 : DC injection braking time 0.1 to 30s (in 0.1s step)
!CAUTION
Do not use the drive brake function for mechanical holding,
otherwise injuries could occur.
Factory Change during
setting operation
Output Freq. | 0.0s | Y |
|
|
3Hz |
Time |
Output voltage