F14 Restart mode after momentary power failure

Change during operation: N = impossible, Y* = possible (enabled by using

FUNC DATA

), Y= possible (enabled by using F15 Frequency limiter (High)F16 Frequency limiter (Low)Manual backgroundManual backgroundManual backgroundManual background )

F14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory

Change during

 

 

F14 Restart mode after momentary power failure

 

 

 

 

 

setting

Operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This function determines whether operation is restarted upon recovery from momentary power failure:

 

 

 

 

 

 

 

 

 

0

Inactive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Failure while drive is stopped:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The stop status is continued after recovery from the failure.

 

 

 

 

 

 

 

Failure during operation:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LU indication is held immediately due to undervoltage and the drive

 

 

 

 

 

 

 

 

trips with alarm output.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

Inactive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Failure while drive is stopped:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The stop status is continued after recovery from the failure.

 

 

 

 

 

 

 

Failure during operation:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LU indication is held upon recovery from the failure and the drive trips

 

 

 

 

 

 

 

with alarm output.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

Active

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The drive restarts with the frequency at the momentary power failure when 0.5s elapses after recov-

 

 

 

 

 

 

 

ery from the fail

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

Active

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The drive restarts with the starting frequency when 0.5s elapses after recovery from the failure.

 

 

 

 

 

 

 

 

 

2

,

 

 

 

 

3

=valid upon recovery from the failure with LU being on. The table below lists ap-

 

 

 

proximate LU indication times for a momentary power failure during operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Drive HP

 

 

1/8

1/4

1/2

1

2

3

5

 

 

[Second]

 

 

 

 

 

 

 

 

3 phase input

0.4

0.6

1.2

1.9

1.7

2.4

4.1

 

 

 

 

 

 

 

 

 

 

 

 

 

Single Phase Input

0.6

1.2

2.6

4.8

3.0

5.0

--

 

 

 

 

F15 Frequency limiter (High)

Factory

Change during

setting

Operation

70Hz

Y

F16 Frequency limiter (Low)

Factory

Change during

setting

Operation

0Hz

Y

This function sets the upper and lower limits of output frequencies.

Manual backgroundManual background 0

to

1 Manual backgroundManual background 2 Manual backgroundManual background 0

0 to 120Hz can be set with a resolution of 1Hz.

If the upper limit and lower limit settings are reversed, the upper limit is valid and the lower limit is ignored.

Hence, the operation is always performed with the upper limit regardless of the frequency setting.