Protection
Item | Specifications | Remarks |
Overload | ∙ Internal electronic thermal overload relay protects drive overload. |
|
Overvoltage | ∙ Detect the excessive DC link circuit voltage to stop drive. |
|
Overcurrent | ∙ Detect overcurrent due to overload on drive output side to protect drive |
|
Incoming surge | ∙ Detect incoming surge voltage between AC power and the earth to protect |
|
| drive. |
|
Undervoltage | ∙ Detect the DC link circuit undervoltage to stop drive |
|
Overheating | ∙ Detects the cooling fan fault or abnormal temperature rise of drive to pro- |
|
tect drive. |
| |
|
| |
∙ Detect overcurrent due to |
| |
Ground fault | ∙ Detects overcorrect due to ground fault on drive output side to protect drive. |
|
(Detect at starting) |
| |
|
| |
Motor protection | ∙ Protect |
|
Input phase fail- | ∙ The drive is protected against phase failure on the input side or |
|
ure protection | due to |
|
(only for |
|
|
200V series) |
|
|
Stall prevention | ∙ Controls frequency to prevent OC trip in case of the output current exceeds |
|
| the limit value during acceleration. |
|
| ∙ Lowers the frequency to hold almost constant torque in case of the output |
|
| current exceeds the limit value during constant speed running. |
|
| ∙ Controls frequency to prevent OU trip in case of the DC link circuit voltage |
|
| exceeds the limit value during deceleration. |
|
Retry | ∙ “Retry” function can be set for the protective functions OC1 to OC3 and |
|
| OU1 to OU3.(No. of times of retry: 5, waiting time: 0.5s fixed. |
|
Dielectric | ∙ At 2000Vac for 1 min. between any main circuit terminals and |
|
strength test | ground.(10mA or less) |
|
Megger test | ∙ At 500Vdc megger test between any main circuit terminals and ground |
|
| (5MΩ or more) |
|
|
|
|
- 82-