GE C11, AF-300 manual Drive output capacity kVA at, ratings

Models: C11 AF-300

1 98
Download 98 pages 7.53 Kb
Page 81
Image 81

2)

Single -phase 200V input series

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Item

 

 

 

 

Specifications

 

 

 

 

Drive HP

1/8

 

1/4

 

1/2

1

 

2

3

Nominal applied motor

1/8

 

1/4

 

1/2

1

 

2

3

 

 

*1 (HP)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated output

0.28

 

0.56

 

1.0

1.6

 

2.8

4.0

ratings

capacity *2 (kVA)

 

 

 

 

 

 

 

 

 

 

 

 

Voltage(V)

3-phase, 200V/50Hz, 200, 220, 230V/60Hz

(Proportional to input voltage)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

Rated current (A)

0.7

 

1.4

 

2.5

4.0

 

7.0

10.0

 

 

 

 

 

 

 

 

 

 

 

Overload capacity

150% of rated current for 1 min.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated frequency (Hz)

50, 60Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Phases, Voltage, Fre-

Single-phase

200 to 240V 50/60Hz

 

 

 

 

 

quency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

supply

Voltage/frequency

Voltage: +10% to –10%, Frequency: +5% to –5%

 

 

Capability for voltage

 

 

When the input voltage drops 165V or more, the drive can be operated continuously.

 

variations

 

 

 

 

 

 

 

 

 

power

dip *3

When the input voltage drops below 165V from rated voltage, the drive can be operated

 

 

 

 

for 15ms.

 

 

 

 

 

 

 

Input

Rated input current *6

1.2

 

2.0

 

3.5

6.5

 

11.8

17.7

 

(with DCR)

 

 

 

 

 

 

 

 

 

 

 

2.3

 

3.9

 

6.4

11.4

 

19.8

28.5

 

(without DCR)

 

 

 

 

Required power sup-

0.3

 

0.4

 

0.7

1.3

 

2.4

3.6

 

ply capacity *4 (kVA)

 

 

 

 

 

 

 

 

 

 

 

 

 

Braking

Braking torque

150

 

 

 

100

 

50

30

 

*5 (%)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DC injection

Starting frequency: 3Hz(fixed),

Braking current (0 to 100%),

 

 

 

braking

Braking current ( 0 to 30%)

 

 

 

 

 

Protective structure

• Closed type IP20

 

 

 

 

 

(IEC60529)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling method

Self-cooling

 

 

 

 

• Fan cooling

 

Weight (Lb)

1.3

 

1.3

 

1.5

2.0

 

3.5

4.9

Notes:

 

 

 

 

 

 

 

 

 

*1 A 4-pole standard motor is assumed as a nominal applied motor.

 

 

 

 

*2

Drive output capacity (kVA) at 230V.

 

 

 

 

 

 

 

*3

When a momentary power failure occurs, while rated voltage is applied 85% of load of nominal motor is

 

 

given.

 

 

 

 

 

 

 

 

 

*4

When an optional power-factor correcting DC reactor is used.

 

 

 

 

*5

Average braking torque where an unloaded motor decelerates and stops from 60Hz

 

 

 

 

operation. (Varies according to the motor efficiency)

 

 

 

 

 

*6

The specification is calculated on assumption that the drive is connected to a 500 kVA-equivalent power

 

 

transformer.

 

 

 

 

 

 

 

 

 

*7

The inter-phase imbalance ratio (%) = ((Max. voltage) - (Min. voltage)) / (Average voltage among three

 

 

phases) x 67

 

 

 

 

 

 

 

 

 

- 79-