GE C11, AF-300 manual Safety Instructions

Models: C11 AF-300

1 98
Download 98 pages 7.53 Kb
Page 3
Image 3
Safety Instructions

Safety Instructions

Read this operation manual carefully and familiarize yourself with the operation of the drive be-

fore installation, connection (wiring), operation or maintenance and inspection of the device. Be

familiar with the drive, safety information, and safety signs before using the drive. In this instruction manual, safety signs are classified into the following categories.

!WARNING

Improper operation may result in death of serious injury.

!CAUTION

Improper operation may result in slight to medium injury or property damage.

Note: More serious situations than those covered by the CAUTION sign can result depending on the circumstances. It is important that you always follow the instructions

Compliance with UL/cUL standards [Applicable to products with UL/cUL mark]

!CAUTION

1.[WARNING] Take care of electric shock. Be sure to turn the drive off before starting work.

2.[CAUTION] When the charge lamp is lit, the drive is still charged at a dangerous voltage.

3.[WARNING] There are two or more live parts inside the drive.

4.The drive is approved as a part used inside a panel. Install it inside a panel.

5.Perform wiring to the input, output and control terminals of the drive, referring to the table below. Use UL certified round crimp terminal to the input and output terminals with insulation cover or covered with reduced tube to obtain the insulation distance. Use a crimping tool recommended by the terminal manufacturer when fabricating crimp terminals.

6.Install a fuse in the power supply to the drive, referring to the table below.

 

 

Tightening torque

Applicable wire diameter

 

Recommended fuse

 

 

Lb Inch[N m]

[AWG] (mm2)2)

Fuse

Voltage

Drive type

 

 

 

 

 

 

[A] 3)

 

 

L1/R, L2/S, L3/T

Control

L1/R, L2/S, L3/T 1)

Control

Gould

Bussmann

 

 

1) U. V. W

section

U. V. W

section

 

Company

Company

input

6KC1123F12X1**

 

 

 

 

3

A4J3

JKS3

6KC1123F25X1**

 

 

 

 

6

A4J6

JKS6

 

 

 

 

 

 

 

 

6KC1123F50X1**

 

 

14 (2.1)

 

10

A4J10

JKS10

230V

10.6 (1.2)

 

 

 

 

 

 

 

 

 

6KC1123001X1**

 

 

 

15

A4J15

JKS15

 

 

 

 

phase

 

 

 

 

 

 

 

 

6KC1123002X1**

 

 

 

 

20

A4J20

JKS20

 

 

 

 

 

 

 

 

6KC1123003X1**

 

 

12 (3.3)

 

30

A4J30

JKS30

3-

 

3.5

20

 

 

 

 

 

 

 

6KC1123005X1**

15.9 (1.8)

10 (5.3)

40

A4J40

JKS40

 

(0.4)

(0.5)

 

 

 

 

 

 

 

230V

6KC1121F12X1**

 

 

6

A4J6

JKS6

 

 

 

 

6KC1121F25X1**

 

 

14 (2.1)

 

6

A4J6

JKS6

 

 

 

 

 

 

 

phase input

6KC1121F50X1**

10.6 (1.2)

 

 

10

A4J10

JKS10

 

 

 

 

 

 

 

 

 

 

 

6KC1121001X1**

 

 

 

 

15

A4J15

JKS15

Single-

 

 

 

 

 

 

 

 

6KC1121002X1**

 

 

12 (3.3)

 

30

A4J30

JKS30

 

 

 

 

 

 

 

 

6KC1121003X1**

15.9 (1.8)

 

10 (5.3)

 

40

A4J40

JKS40

 

 

 

 

 

 

 

 

 

 

 

 

1)Only the L1/L and L2/N phases are provided for the single-phase 230V input series.

2)Use copper wires of allowable maximum temperature 60 or 75 °C.

3)Use UL certified "fast acting fuse."

Connect the power supply satisfying the characteristics shown in the table below as an input power supply of the drive. (Short circuit rating)

Drive type

Input max. volta

Input current

 

 

 

3 Phase input

AC230V

5,000 A or less

Single phase input

AC240V

 

-1-

Page 3
Image 3
GE C11, AF-300 manual Safety Instructions