Heat sink overheat- ing (OH1)

(3) Undervoltage(LU)

(4)Overheating of heat sink (OH1)

LU

Heat sink overheat- ing (OH1)

 

Has (momentary) power fail-

Yes

Reset and restart opera-

 

 

 

 

 

 

ure occurred?

 

 

tion. (If F14 is 0,1)

 

 

 

 

 

 

 

 

 

 

No

Yes

 

 

 

 

 

 

 

 

Faulty parts or loose connec-

Replace faulty parts and

 

 

 

 

 

 

tion in power control circuit?

 

 

fix connection.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Load excessive?

No

Cooling fan rotating?

Yes

Replace cooling fan.Reduce load.

No

Replace cooling fan.

 

No

 

 

 

No

Power supply voltage within

 

Yes

specified value?

Yes

 

Any load requiring large

Yes

 

starting current within the

 

 

same power distribution

 

 

group?

 

 

 

 

 

 

 

No

 

 

 

 

Yes

 

Does LU activate when cir-

 

 

 

cuit breaker or magnetic con-

 

 

tractor switched to ON?

 

 

 

 

 

 

 

No

 

 

 

 

 

 

Probable faulty control circuit

 

 

of drive or error because of

 

 

noise, etc. Contact GE Fuji

 

 

 

 

 

Modify power distribu- tion system to satisfy specified value.

Power transformer ca- pacity adequate?

Yes

Probable faulty drive. Contact GE Fuji

Cooling air passage blocked up?

No

Ambient temperature within specified value?

Yes

Probable faulty drive or error because of noise, etc. Contact GE

Fuji.

Yes Remove obstacles.

No Arrange peripheral Manual backgroundconditions to secure

specified value.

(5) External alarm input (OH2)

OH2

Signal from external de- vice connected between control circuit terminals THR - CM?

Yes

No

Connect alarm signal con- tact. Short-circuit between terminals THR - CM if no signal is input.

Is the alarm function of the external device operat-

ing correctly?

Yes

No

Probable faulty drive or

error because of noise.

 

 

Contact GE Fuji.

 

 

 

 

 

Remove the cause of alarm function activation.

-63-