Change during operation: N = impossible, Y* = possible (enabled by using FUNCDATA

), Y= possible (enabled by using )

F27 Motor sound (sound tone)

Factory

Change during

setting

operation

0

Y

This function adjusts the motor operation sound when a value of 7 or less is set with function F26.

0

to

3

Level 0

Level 3

F30

FM terminal (voltage adjust)

 

Factory

Change during

setting

operation

 

100%

Y

This function regulates the frequency meter voltage level output to the FM terminal in the range from 0 to 200% (in 1% step).

0 (Full scale about 0Vdc)

to

2 0 0

(Full scale about 11Vdc)

 

11V

200%

 

Note : Output to the FM terminal is pulse output

 

 

 

 

Output

10V

 

100%

with constant frequency and variable duty.

voltage

 

 

 

Variable

 

5V

 

50%

Approx. 13V

 

 

 

 

 

 

50%

100%

 

Output/full scale

F31 FM terminal (Function)

Fixed to 121.6Hz

Factory

Change during

setting

operation

 

0

Y*

This function selects the contents of output to the FM terminal.

0 Output frequency (maximum output frequency = 100%)

1 Output current (drive rated current x 2 = 100%)

2 PID feedback value (full scale = 100%) 3 DC link circuit voltage (500Vdc = 100%)

-50-

Page 52
Image 52
GE AF-300, C11 manual F27 Motor sound sound tone, F30 FM terminal voltage adjust, F31 FM terminal Function