GE C11, AF-300 manual Trial Run, 3-1 Running command

Models: C11 AF-300

1 98
Download 98 pages 7.53 Kb
Page 31
Image 31

3-3 Trial Run

The motor rotates when a frequency value and running command are input from the keypad panel or external signal terminal. Refer to Table 3-3-1.

Use a low frequency (about 5Hz) for trial runs

A frequency can be set using the built-in frequency setting POT (VR) , and forward/stop can be performed using the keypad panel with the functions set in the factory.

Table 3-3-1 Running command

Operation method

Frequency setting

Running command

Operation by using

(When built-in POT (VR) is used)

Operation starts when the

keypad panel

The frequency increases when the variable

RUN key is pressed.

 

resistor is turned clockwise and reduces

 

The motor decelerates and

 

when it is turned counterclockwise. The mo-

 

stops when the STOP key is

 

tor accelerates when the variable resistor is

pressed.

 

turned clockwise during operation and de-

 

 

 

celerates when it is turned counterclockwise.

 

 

 

 

Operation by using

(When the UP/DOWN key is used)

Operation starts when FWD

external signal ter-

(REV) terminal is connected.

minal

Frequency increases when the UP key is

The motor decelerates and

 

 

pressed.

 

stops when the FWD (REV)

 

It reduces when the DOWN key is pressed.

 

terminal is disconnected.

 

 

 

 

* Operation is not stopped

 

 

although the STOP key is

 

 

pressed. (When the data of

 

 

F02 is set to “2” or “4”)

Check the following items:

a)Rotation direction

b)Whether rotation is smooth (whether there is a motor buzzing noise or abnormal vibration)

c)Whether acceleration and deceleration are smooth

d)Whether the drive cooling fan is rotating (1.5kW or more)

If no abnormality is detected, check the item again by increasing the frequency.

Even if the output from the drive is stopped, you will be get an electric shock when you touch the main circuit terminals such as drive output terminals U, V and W if the voltage is supplied to the main power supply input terminal.

The smoothing capacitor in the drive has been charged when the power is turned off and it is not dis- charged immediately. Before touching the electric circuit, wait until at least five minutes have elapsed after power-off and the charge lump is off, indicating the voltage is already low.

After checking normality in the above trial run, start operation.

-29-

Page 31
Image 31
GE C11, AF-300 manual Trial Run, 3-1 Running command