6 Protective Function
6-1 List of protective functions
When the protective function is activated, drive output is instantly cut off (while the motor coasts until it is stopped), and an alarm is issued, and the details of the alarm are displayed on the keypad panel.
|
| Table | |||
| Keypad |
|
|
| |
Alarm Name | panel dis- |
|
| Contents of operation | |
| play |
|
|
| |
Overcurrent | OC1 | During acceleration |
| If the drive output current momentarily exceeds the over- | |
|
| ||||
| OC2 | During deceleration |
| current detection level because of an overcurrent in the | |
|
|
| |||
| OC3 | While running at |
| motor or the | |
| constant speed |
| |||
|
|
| shut down, an alarm is issued, and the drive is tripped. | ||
|
|
|
| ||
Overvoltage |
| During acceleration |
| If the DC voltage of the main circuit exceeds the overvolt- | |
OU1 |
| age detection level because of an increase in the regenerat- | |||
|
| ||||
|
|
|
| ing current from the motor, etc., output is shut down, an | |
| OU2 | During deceleration |
| alarm is issued, and the drive is tripped. However, protec- | |
|
| tion against inadvertent overvoltage loading (e.g., high- | |||
|
|
|
| voltage line) might not be provided. | |
| OU3 | While running at |
| ||
|
|
| |||
| constant speed |
|
| ||
|
|
|
| ||
Undervoltage | LU | If the DC voltage of the main circuit falls below the undervoltage detection level | |||
|
| because of a lowered power supply, output is shut down to protect the drive. If the | |||
|
| restart function after momentary power failure is not activated, an alarm is issued | |||
|
| and the drive is tripped. |
| ||
|
| If the restart function is activated, the drive restarts automatically with no alarm. | |||
|
| For further details of the protective function, refer to the descriptions of Function | |||
|
| F14. |
| ||
Overheating of | OH1 | If the temperature of the heat sink used for cooling the rectifier diodes and IGBTs | |||
heat sink | |||||
| rises because of cooling fan failure, etc., protective function is activated to stop | ||||
|
| ||||
|
| operation, an alarm is issued, and the drive is tripped. | |||
External Alarm | OH2 | If the control circuit terminal THR (functional change of X1 to X3 terminals) is | |||
| set to OFF, an alarm is issued and the drive is tripped. | ||||
|
| ||||
| OL | If the motor current exceeds the operating level set by the electronic thermal O/L | |||
Motor overload |
| relay, output is shut down to protect the motor, an alarm is issued, and the drive is | |||
|
| ||||
|
| tripped. |
| ||
Drive overload | OLU | If the output current exceeds the drive rated overload current, output is shut down, | |||
| an alarm is issued, and the drive is tripped. | ||||
|
|