| Item | Specifications | Remarks |
| Frequency jump | ∙ Jump frequency (3 points) and jump hysteresis width (1 point) can be pre- |
|
Control | control | set. |
|
Restart after |
|
| |
momentary | ∙ Drive restarts without causing |
| |
| power failure |
|
|
| PID control | ∙ PID control function is provided standard. |
|
Enclosure | ∙ IP20 |
| |
(IEC 60529) |
|
| |
Cooling method | ∙ Natural cooling for 1 HP or less, Fan cooling for 2 HP or more |
| |
| Running, | ∙ Output frequency, output current, and PID reference value/feedback value |
|
| stopped | The CRG lamp is on when the capacitor is charged. |
|
| Program mode | ∙ Function code and data code |
|
| Tripped | [Cause of trip by code] |
|
|
| ∙ OC1 (Overcurrent: during acceleration) |
|
|
| ∙ OC2 (Overcurrent: during deceleration) |
|
|
| ∙ OC3 (Overcurrent: while running at constant speed) |
|
|
| ∙ OU1 (Overvoltage: during acceleration) |
|
|
| ∙ OU2 (Overvoltage: during deceleration) |
|
Indication |
| ∙ OU3 (Overvoltage: while running at constant speed) |
|
| ∙ LU (Undervoltage) |
| |
| ∙ OH1 (Overheating: Heat sink) |
| |
| ∙ OH2 (Overheating: External alarm) |
| |
|
|
| |
|
| ∙ OL (Overload: Motor) |
|
|
| ∙ OLU (Overload: Drive) |
|
|
| ∙ Er1 (Memory error) |
|
|
| ∙ Er3 (CPU error) |
|
|
| ∙ Er6 (Operation error) |
|
|
| ∙ Er8 (RS485 communication error) |
|
|
| ∙ Lin (Input phase failure) |
|
| Running, | ∙ Fault history data is stored and indicated for the past four trips. Data is |
|
| Tripped | retained while power is off. |
|
- 81-