GE C11, AF-300 manual Memory error Er1 Abnormal dis- play or indica- tion goes out

Models: C11 AF-300

1 98
Download 98 pages 7.53 Kb
Page 67
Image 67
(7) Memory error (Er1)

(7) Memory error (Er1)

Abnormal dis- play or indica- tion goes out

CPU error (Er3)

Memory error Er 1

CPU error Er 3

Analog frequency set to negative value?

No

Yes

 

Turn power OFF then ON again after CHARGE lamp has gone out.

Reset analog frequency to positive value.

Is data displayed on LED?

Yes

No

Noise source nearby?

No

Yes

Remedy faulty parts.

Drive is normal. Continue operation.

Probable faulty drive. Contact GE Fuji.

(8) RS485 Communication Error (Er8) [In case RS485 communication is not used]

Communication

Error Er8

o00 is set to 1?

Yes

No

Probable faulty drive. Manual background Contact GE Fuji.

Set o00 to 0.

*For Er8 measures when using RS485, refer to the instruction manual for optional RS485 communication card.

-65-

Page 67
Image 67
GE C11, AF-300 manual Memory error Er1 Abnormal dis- play or indica- tion goes out