GE C11 Starting frequency, Stop frequency, F26 Motor sound carrier freq, 0.2Hz, 1 1kHz 2 2kHz

Models: C11 AF-300

1 98
Download 98 pages 7.53 Kb
Page 51
Image 51
Starting frequency

Change during operation: N = impossible, Y* = possible (enabled by using

FUNC DATA

), Y= possible (enabled by using Stop frequency0.2HzF26 Motor sound (carrier freq.)1 : 1kHzManual backgroundManual background )

F23

Starting frequency

 

 

 

Factory

Change during

 

 

 

setting

Operation

 

 

 

 

 

 

 

 

 

 

 

 

F23

1Hz

N

 

 

 

 

 

 

 

F25

Stop frequency

F25

1Hz

N

 

 

 

 

These functions set a starting or stop frequency in a range Starting frequency ￿ stop frequency

 

from 1 to 6Hz in 1Hz step.

 

 

1

1Hz

Starting

to

 

frequency setting

 

Stop

6

6Hz

frequency setting

Output frequency in forward/

t

 

reverse operation

Starting frequency < stop frequency

Stop frequency setting

Starting frequency setting

Starting frequency setting

Stop frequency setting

FWD

REV

Data cannot be

F24

changed.

0.2Hz

Stop

frequency setting Starting frequency setting

t

If the set frequency is lower than the stop frequency, the drive output is 0Hz.

Factory

Change during

setting

operation

0.0

-

F26 Motor sound (carrier freq.)

Factory

Change during

setting

operation

2kHz

Y

This function changes the motor tone quality by changing the carrier frequency.

Manual backgroundManual background 0

to Manual background Choose among 16 types according to the usage conditions.

Manual backgroundManual background 1 Manual backgroundManual background 5

Data code 0 : 0.75kHz (Low carrier)

1 : 1kHz

2 : 2kHz

15 : 10kHz (High carrier, low noise)

Note: When the drive is operating at 9kHz or higher carrier frequency, the carrier frequency for may be reduced to 8kHz automatically to protect the drive.

-49-

Page 51
Image 51
GE C11, AF-300 manual Starting frequency, Stop frequency, F26 Motor sound carrier freq, 0.2Hz, 1 1kHz 2 2kHz