Message

 

 

 

 

 

 

Description

 

 

FCI_E3:#1 FYI. Use a DA called <%s> to expose

Refer to Appendix B.1

 

diagnostic info., FCI_E3_STATS_DA )

 

 

 

 

 

 

FCI_E3:#2 FYI. Added Event Desc=<%s> Index=%d

Printed for information only. No action

Categ=%d

 

,

new_event_desc

,

required if it confirms your expectations.

new_event_desc_index_value , new_event_desc_categ ) ;

 

 

 

 

FCI_E3:#3 Err. No space. Reject Event Desc=<%s>

There is only space for 60 event types.4

Index=%d

 

,

new_event_desc

,

new_event_desc_index_value ) ;

 

 

 

 

 

 

FCI_E3:#4

FYI.

Duplicate

Event

Desc=<%s>.

,

The Event type being added already

new_event_desc ) ;

 

 

 

 

 

exists. If you are updating the category,

FCI_E3:#5

FYI.

Duplicate

Event

Desc=<%s>.

,

ignore the message. Otherwise correct the

new_event_desc ) ;

 

 

 

 

 

configuration file.4

 

FCI_E3:#6

Err. Event Index=%d. Too big to set bit.,

If the event index is greater than 64 then

the data cannot be stored as bits - only 64

drv_bd->event_index )

 

 

 

 

bits are reserved for events.

 

 

 

 

 

 

 

FCI_E3:#7a Err. DA=%s too short. Rqd=%d, dt-

The MD in question has a length and

>buffer_name , offset );

 

 

 

 

offset which makes it run past the end of

FCI_E3:#7b Err. DA=%s too short. Rqd=%d, possible_md-

the Data Array. Message 7b is printed

>data->buffer_name , offset );

 

 

 

 

when data is being stored as bits.4

FCI_E3:#8 FYI. Reset was rcvd and processed! Stamped

Printed for information only. No action

%s %s , drv_bd->time , drv_bd->date )

 

 

required.

 

 

 

 

 

 

 

 

 

A reset was received but the driver could

FCI_E3:#9 Err. Reset was ignored.

 

 

 

not reset any

data.

'Clear_on_Reset'

 

 

 

 

 

 

 

possibly set to 'no' on all Map Descriptors?

FCI_E3:#10 FYI. Reset of DA=%s Off=%d Len=%d,

Printed for information only. No action

possible_md->data->buffer_name

,

possible_md-

required.

 

 

>bxi_data_buffer_offset , possible_md->data_length );

 

 

 

 

FCI_E3:#11 Err. Cant reset DA=%s len=%d rqd=%d,

 

 

 

possible_md->data->buffer_name

 

 

,

The Map Descriptor in question has a

da_get_length_in_items ( (DAH_TYP) possible_md->data )

length and offset which makes it run past

,

possible_md->data_length+possible_md-

the end of the Data Array.4

>bxi_data_buffer_offset );

 

 

 

 

 

 

 

FCI_E3:#12a Err. No MD's to store message data.

 

The Driver could not find a place to store

 

 

 

 

 

 

 

data from a message received. If the data

 

 

 

 

 

 

 

FCI_E3:#12b Err. No MD's to store message data."

 

is not required then the message may be

 

 

 

 

 

 

 

ignored.

Otherwise

update the

FCI_E3:#13 Err. Msg was ignored. MD Required for

configuration file4.

 

Storage.

 

 

 

 

 

 

 

 

 

FCI_E3:#13a Err. Diagnostic 1);

 

 

 

Take a log. Try and repeat the event that

FCI_E3:#13b Err. Diagnostic 2);

 

 

 

caused the message to be printed. Then

FCI_E3:#13c Err. Diagnostic 3);

 

 

 

contact tech support.

 

FCI_E3:#14

Err.

<%s>

file

not

found., md-

 

 

 

>mapdesc_name ) ;

 

 

 

 

 

If this error is repeated often it is possible

FCI_E3:#15 Err. Event Type=<%s> Not recognized." ,

that a FCI firmware update has made the

drv_bd->event_desc )

 

 

 

 

driver unusable. Take a log and contact

FCI_E3:#16 Err. Point Type='%c'(%#x) Not recognized. ,

tech support.

 

 

drv_bd->point_identifier[0] , drv_bd->point_identifier[0] ) ;

 

 

 

 

4Correct the configuration file, download to the FieldServer and restart the FieldServer for the changes to take effect.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com

Image 17
Contents Effective for all systems manufactured after September Driver Manual FS-8700-132 Gamewell FCI E3 Series SerialTable of Contents Max Nodes Supported Gamewell FCI-E3 Series Serial Driver DescriptionILI-MB-E3 Board GND TB6FCI-E3 Data Arrays/Descriptors FCIE3 Client Side Node Descriptors Driver Related Map Descriptor Parameters Manual Station L1M21 003728 01/01/99CRLF First Alarm UP Stairs N. ENTDarelay FS-8700-132 Gamewell FCI-E3 Driver Manual FS-8700-132 Gamewell FCI-E3 Driver ManualPage 13 Destroyed FCIE3 TroubleDamodu ANY Appendix A.5.1 Networked Panels Appendix A.4. Panel SynchronizationFYI Page Appendix B.1. Driver Stats Exposed FCIE3STATNOPLACETOSTORENODE FCIE3STATPARSEDNOERRSEXCLDRESETFCIE3STATRCVDMSGS