Appendix A. Troubleshooting Tips

Every 2nd message Times Out A possible cause is that the poll frequency is so low that the time between polls is greater than the Max Link Idle Time (of the PLC). If the time is exceeded the connection is closed. Thus when the next poll is received by the PLC it ignores it and hence it times out in the FieldServer. After timing out, the driver re-establishes the connection for the next poll.

Very slow Comms Rate A timer known as the T1 timer is the minimum time that must pass before a response to a message can be sent. Both ends of a SNP connection have their own T1 timer (hard coded in the driver). When a connection is made the timers are exchanged and the larger of the two is used. The drivers T1 timer is set to a very small number. SNP message #6 indicates the size of the T1 timer. You may need to configure the PLC to improve communications.

Multidrop RS-485 networks. SNP protocol specifies that their may only be one master on a network at a time. When using nameless Nodes (Node_id=0) there may be one and only one PLC on the connection.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldServer.com

Image 19
Contents Applicability & Effectivity FS-8700-66 GE SNPTable of Contents 3 of 29FS-8700-66GE-SNP Manual Gesnp Description4 of 29FS-8700-66GE-SNP Manual 5 of 29FS-8700-66GE-SNP Manual Hardware ConnectionsFS-8917-01 From FieldServer 6 of 29FS-8700-66GE-SNP ManualGE Logicmaster 7 of 29FS-8700-66GE-SNP ManualData Arrays/Descriptors Configuring the FieldServer as a Gesnp Client8 of 29FS-8700-66GE-SNP Manual 9 of 29FS-8700-66GE-SNP Manual Client Side Connection DescriptorsSNP Descriptor Client Side Node Descriptors10 of 29FS-8700-66GE-SNP Manual RDBC, WRBC, WrbxTiming Parameters Driver Related Map Descriptor Parameters11 of 29FS-8700-66GE-SNP Manual Map Descriptor Example 2 Simple Write Map Descriptor Example 1 Simple Read12 of 29FS-8700-66GE-SNP Manual 13 of 29FS-8700-66GE-SNP Manual Map Descriptor Example 3 Handling Bits19200 Odd None Configuring the FieldServer as a Gesnp ServerServer Side Connection Descriptors 14 of 29FS-8700-66GE-SNP Manual15 of 29FS-8700-66GE-SNP Manual Server Side Node Descriptors16 of 29FS-8700-66GE-SNP Manual Driver Specific Map Descriptor Parameters17 of 29FS-8700-66GE-SNP Manual 18 of 29FS-8700-66GE-SNP Manual Map Descriptor ExampleTabler 19 of 29FS-8700-66GE-SNP Manual Appendix A. Troubleshooting Tips20 of 29FS-8700-66GE-SNP ManualPage 20 Appendix B. Error MessagesSNP9 Edit the CSV, correct the problem and reset the FieldServer Appendix B.1. Driver Stats Gestatmboxplcstat Gestatmboxprivlvl DrvdlltimeoutDrvdllerror DrvdllerrorcodeGestatdrvactnakr GestatcdupdictimeoutGestatdrvactnodatar Gestatdrvactnonoder25 of 29FS-8700-66GE-SNP Manual Appendix C. Advanced Topics Appendix C.1. SNP Node NamesAppendix C.2. Scaling Minor Error Status Codes26 of 29FS-8700-66GE-SNP Manual 27 of 29FS-8700-66GE-SNP Manual 0BD Minor Error Status Codes Program Load and Store Requests28 of 29FS-8700-66GE-SNP Manual 0BFThis page Intentionally Left Blank 29 of 29FS-8700-66GE-SNP Manual