FieldServer FS-8700-24 instruction manual Server Side Connection Descriptors

Page 7

FS-8700-24 ControlNet Driver Manual

Page 7 of 12

4.Configuring the FieldServer for Unscheduled ControlNet Access with PCCC messaging

For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” sample files provided with the FieldServer).

This section documents and describes the parameters necessary for configuring the FieldServer to communicate with ControlNet devices using PCCC messaging. This transfer mechanism would be used to communicate between the FieldServer and PLC-5 controllers.

The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for ControlNet communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the FieldServer virtual node(s) needs to be declared in the “Nodes” section, and the data to be transferred needs to be mapped in the “Unscheduled Map Descriptors” section. Details on how to do this can be found below.

Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

4.1.Server Side Connection Descriptors

Section Title

 

 

Connections

 

 

Column Title

Function

Legal Values

Adapter

Adapter Name

ControlNet

Protocol

Specify protocol used

ControlNet

Example

//Connections

Connections

 

Adapter,

Protocol

ControlNet,

ControlNet

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com

Image 7
Contents FS-8700-24 ControlNet Table of Contents ControlNet Description FieldServer Technologies Description Provided by the Supplier of 3rd Party EquipmentFS-x40 Hardware ConnectionsConnection Notes Server Side Connection Descriptors ControlNet Node Descriptors Unscheduled Map Descriptors using Pccc messagingFieldServer Specific Map Descriptor Parameters Timing Parameters Driver Specific Map Descriptor ParametersFollowing Map Descriptor will read data from a PLC5 Unscheduled Map Descriptor ExampleAppendix A.2. Map Descriptor functions Appendix A. Advanced Topics Appendix A.1. Write-throughsThis page Intentionally Left Blank