FieldServer FS-8700-40 instruction manual Rdbc

Page 12

FS-8700-40 SBT FSI Driver Manual

Page 12 of 29

 

 

4.4.4 Map Descriptor example 1 - Monitoring a MXL/XLS Device for Events

To monitor a MXL/XLS device we need only one “poller” Map Descriptor as shown below. The function of this Map Descriptor’s is to continuously check the MXL device for events from panels. Only one poller Map Descriptor per FieldServer port is required when monitoring more than one MXL/XLS device. The Node_Name will indicate on which port this Map Descriptor resides.

// Client Side Map Descriptors

 

 

 

 

 

 

Map_Descriptors

 

 

 

 

 

 

 

Map_Descriptor_Name ,Data_Array_Name

,Data_Array_Offset

,Function

,Node_Name

,Block_Number

,Length

,Msg_Type

CD_Poller1

,Event_Counts1

,0

,RDBC

,Panel1

,1

,19

,poller

 

 

Choose a

 

Specify length

 

 

 

 

in multiples of

 

 

 

Node_Name

 

 

 

 

 

19 events

 

Specifies Data Array

Specifies

from the

 

 

 

according to

 

that will hold event

offset into

passive Map

 

 

Specifies lowest panel

Block Number

 

counters. Data Array

event

Descriptors in

 

number from which

used.

Specify poller

length must be equal

counters

the next section

events will be

 

message type

or greater than Data

Data Array

to specify the

Refer to

received. Refer to

for this Map

Array offset plus Map

where event

port on which

Appendix A for more

Appendix A

Descriptor.

Descriptor length.

counts will be

this poller will

information.

for more

 

 

stored.

be active.

 

 

 

information.

 

 

 

 

 

 

CD – Client Descriptor

FieldServer Technologies 1991 Tarob Court Milpitas, California

95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509

1970 email: support@fieldserver.com

Image 12 Contents
Applicability & Effectivity Sierra Monitor CompanyTable of Contents Required 3r d Party Configuration Supplied by FieldServer Technologies for this driverProvided by the Supplier of 3rd Party Equipment Hardware FS-8700-40 SBT FSI Driver ManualUsing the NIM-1R or NIM-1W for MXL Hardware ConnectionsFSI Connection Notes FSIConfiguring the Fieldserver AS a SBT-FSI Client FS-8700-40 SBT FSI Driver Manual Data Arrays Section TitleColumn Title Function Legal Values ExampleClient Side Connection Descriptions SBT-FSIMXL, XLS Second ExampleClient Side Node Descriptors Driver Related Map Descriptor Parameters Timing ParametersFS-8700-40 SBT FSI Driver ManualPage 11 XLSRdbc FS-8700-40 SBT FSI Driver Manual Map Descriptor example 2 Monitoring Analog Loop Devices Advanced Client Configuration Using Bidirectional Capability Configuring the Fieldserver AS a SBT-FSI Server Device TypeServer Side Connection Descriptors NoneServer Side Node Descriptors Driver Specific Map Descriptor Parameters FS-8700-40 SBT FSI Driver ManualPage 19FS-8700-40 SBT FSI Driver Manual FS-8700-40 SBT FSI Driver Manual Appendix A.1. Specifying a Poller Map Descriptor length Example 1 Only receive events from panelExample 2 Receive events from panel 7 Appendix A.2. Interpreting Panel Error Messages TroubleAppendix A.4. Using Trouble Codes MXL/XLS Trouble CodesInput DE-ISOLATED Input IsolatedBell 2 Isolated Bell 2 DE-ISOLATEDFS-8700-40 SBT FSI Driver Manual Appendix A.5. Activating and De-activating Entities MXLAppendix A.6. Arming and De-Arming Entities MXLXLS