FieldServer FS-8700-40 instruction manual Appendix A.2. Interpreting Panel Error Messages, Trouble

Page 23

FS-8700-40 SBT FSI Driver Manual

Page 23 of 29

 

 

Appendix A.2. Interpreting Panel Error Messages

A NAK is sent by the panel when it is unable to respond to a message. The format will be as follows:

T02> DRV-> CER : Panel replied with NAK on last message!

T02> DRV-> CER : Reason: 1

The following table lists the reason for the failure and the suggested corrective action. Note that the messages are generated by the panel, not the FieldServer.

Reason #

Error

Corrective Action

Reason 1

Checksum or Parity

Ensure connection baudrate, start, stopbits and parity match the panel's

fail

settings

 

 

 

 

Reason 2

Receive buffer full

Increase scan interval on the poller Map Descriptor.

 

 

 

Reason 3

Syntax Error

Check integrity of physical connection to panel, route cables away from

electromagnetic sources that can generate noise.

 

 

 

 

 

Reason 4

Unrecognized

Replace hardware?

message failure

 

 

 

 

 

Appendix A.3. Obtaining Point Addresses from the panel report

In order to configure the FieldServer to capture data from the Panel, the point addresses being used in the panel need to be identified. The Panel report that can be printed out from the panel can be used for this purpose, but matching the Report parameters with the FieldServer configuration parameters is not a trivial exercise. The following notes should assist in identifying the addresses needed for FieldServer configuration

The preamble to the report is not relevant to the FieldServer Driver.

The first Module can be identified by the title NET Address =1. This corresponds to FieldServer’s “Block 1”.

The Module Subaddress corresponds to individual points in the Block Array.

This information is depicted in the following file extract:

Corresponds to Block Number 1

NET ADDR: 1 ==> ALD-2 2 Analog Loop Module

Page: 5

===============================================================================

Corresponds to Block Array point 1

Module Subaddress ----------------

> 1

DEVICE TYPE ----------------------

> TRI-60/TRX-2/3 1 Switch Input

Usage --------------------------

> TROUBLE

Message ------------------------

> RCP-01 Trouble Input MM-1

Switch Contact Type -----------

> N.O.

FieldServer Technologies 1991 Tarob Court Milpitas, California

95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509

1970 email: support@fieldserver.com

Image 23
Contents Sierra Monitor Company Applicability & EffectivityTable of Contents FS-8700-40 SBT FSI Driver Manual Required 3r d Party ConfigurationSupplied by FieldServer Technologies for this driver Provided by the Supplier of 3rd Party Equipment HardwareHardware Connections Using the NIM-1R or NIM-1W for MXLFSI FSI Connection NotesConfiguring the Fieldserver AS a SBT-FSI Client FS-8700-40 SBT FSI Driver Manual Example Data ArraysSection Title Column Title Function Legal ValuesSecond Example Client Side Connection DescriptionsSBT-FSI MXL, XLSClient Side Node Descriptors XLS Driver Related Map Descriptor ParametersTiming Parameters FS-8700-40 SBT FSI Driver ManualPage 11Rdbc FS-8700-40 SBT FSI Driver Manual Map Descriptor example 2 Monitoring Analog Loop Devices Advanced Client Configuration Using Bidirectional Capability Device Type Configuring the Fieldserver AS a SBT-FSI ServerNone Server Side Connection DescriptorsServer Side Node Descriptors FS-8700-40 SBT FSI Driver ManualPage 19 Driver Specific Map Descriptor ParametersFS-8700-40 SBT FSI Driver Manual FS-8700-40 SBT FSI Driver Manual Example 2 Receive events from panel 7 Appendix A.1. Specifying a Poller Map Descriptor lengthExample 1 Only receive events from panel Trouble Appendix A.2. Interpreting Panel Error MessagesInput Isolated Appendix A.4. Using Trouble CodesMXL/XLS Trouble Codes Input DE-ISOLATEDBell 2 DE-ISOLATED Bell 2 IsolatedFS-8700-40 SBT FSI Driver Manual MXL Appendix A.5. Activating and De-activating EntitiesMXL Appendix A.6. Arming and De-Arming EntitiesXLS

FS-8700-40 specifications

The FieldServer FS-8700-40 is an advanced protocol gateway that plays an essential role in the integration of diverse building management systems and industrial automation environments. Renowned for its robustness and versatility, the FS-8700-40 is engineered to facilitate seamless communication between a variety of devices and networks, which enhances operational efficiency and flexibility.

One of the standout features of the FS-8700-40 is its support for multiple protocols. The device is compatible with a wide range of protocols prevalent in the industry, including BACnet, Modbus, LonWorks, and many others. This multi-protocol capability allows users to connect devices from different manufacturers without the need for extensive customization or the installation of multiple gateways, thus simplifying system architecture and reducing costs.

The FS-8700-40 is equipped with a powerful microprocessor that ensures high performance and reliability. Its processing capabilities enable it to handle complex data exchanges and logic operations, making it suitable for both small scale and large scale applications. The device also features an extensive memory capacity, aiding in the storage and retrieval of large datasets necessary for sophisticated control strategies and reporting functionalities.

Another prominent characteristic of the FS-8700-40 is its user-friendly interface. The device comes with a web-based graphical user interface (GUI) that allows for easy configuration and monitoring. Users can easily set up and modify communication parameters, visualize data trends, and implement system changes in real time, all from an accessible online portal. This enhances user experience and decreases the time needed for system maintenance and updates.

Security is also a critical consideration in the design of the FS-8700-40. The device incorporates advanced security measures to protect sensitive data and ensure secure communication between connected devices. This includes features such as user authentication, data encryption, and secure sockets layer (SSL) support, which fortify the overall integrity of the system.

In addition to its technological prowess, the FS-8700-40 is designed to be highly durable and reliable in various operational conditions. With features like temperature resistance and surge protection, it boasts an extended lifespan and requires minimal maintenance, making it a cost-effective solution for users.

In summary, the FieldServer FS-8700-40 stands out due to its multi-protocol support, high processing capabilities, user-friendly interface, robust security, and durability. Its ability to facilitate communication between heterogeneous systems makes it an indispensable tool for businesses looking to optimize their operational efficiency and future-proof their infrastructure.