4. Configuring the FieldServer as a Notifier AM6000 Client
For a detailed discussion on FieldServer configuration, please refer to the instruction manual for the FieldServer. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” files on the driver diskette).
This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a Notifier AM6000 Server.
The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for Notifier AM6000 communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the destination device addresses need to be declared in the “Client Side Nodes” section, and the data required from the servers needs to be mapped in the “Client Side Map Descriptors” section. Details on how to do this can be found below.
Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.
4.1 Data Arrays
Section Title |
|
|
Data_Arrays |
|
|
Column Title | Function | Legal Values |
Data_Array_Name | Provide name for Data Array | Up to 15 alphanumeric characters |
Data_Format | Provide data format. Each data array | FLOAT, BIT, UInt16, SInt16, |
| can only take on one format. | Packed_Bit, Byte, Packed_Byte, |
|
| Swapped_Byte |
Data_Array_Length | Number of Data Objects. Must be larger | |
| than the data storage area required for |
|
| the data being placed in this array. |
|
|
|
|
Example
//Data Arrays
Data_Arrays
Data_Array_Name, Data_Format, Data_Array_Length
DA_AI_01, | UInt16, | 200 |
DA_AO_01, | UInt16, | 200 |
DA_DI_01, | Bit, | 200 |
DA_DO_01, | Bit, | 200 |
FieldServer Technologies 1991 Tarob Court, Milpitas, California 95035 (408)
Visit our website: www.fieldserver.com