FieldServer FS-8700-123 Client Side Connection Descriptions, Client Side Node Descriptors, Hf Cnc

Page 8

FS-8700-123 MetOne Particle Counter Serial Driver Manual

Page 8 of 26

4.2.Client Side Connection Descriptions

Section Title

 

 

 

 

 

Connections

 

 

 

 

 

Column Title

 

Function

 

 

Legal Values

 

Specify which port the device

 

Port

is

connected

to

the

P1-P8, R1-R21

 

FieldServer

 

 

 

Protocol

Specify protocol used

 

MetOne

Baud*

Specify baud rate

 

 

9600 (Vendor limitation).

Parity*

Specify parity

 

 

None (Vendor limitation)

Data_Bits*

Specify data bits

 

 

8 (Vendor limitation)

Stop_Bits*

Specify stop bits

 

 

1 (Vendor limitation)

Handshaking*

Specify

hardware

RTS, RTS/CTS, None

 

handshaking

 

 

 

Poll_Delay*

Time between internal polls

 

0-32000 seconds, 0.05 seconds

Example

//Client Side Connections

Connections

Port,

Protocol,

Baud,

Parity,

Handshaking,

Poll_Delay

P8,

MetOne,

9600,

None,

None,

0.100s

4.3.Client Side Node Descriptors

 

Section Title

 

 

 

 

 

 

Nodes

 

 

 

 

 

 

Column Title

Function

Legal Values

 

 

Node_Name

Provide name for node

Up to 32 alphanumeric characters

 

 

Node_ID

The ‘Device’ Number

1-64

 

 

 

Protocol

Specify protocol used

MetOne.

 

 

 

Connection

Specify which port the device is

P1-P8, R1-R21

 

 

 

 

connected to the FieldServer

 

 

 

 

 

Identifies for the driver the family

“237 Family”

 

 

 

 

“2408” or “Manifold”

 

 

PLC_Type

of Particle

Counters/Manifolds

“4800”

 

 

 

 

connected to.

 

“HF CNC”

 

 

 

 

 

 

 

 

 

Example

 

 

 

 

 

 

 

 

 

 

 

 

 

Nodes

 

 

 

 

 

 

Node_Name,

Node_ID,

Protocol,

PLC_Type,

Connection

 

 

PLC 1,

1,

MetOne,

237 Family,

P8

 

1Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: 408 262-2299 Fax: 408-262-2269 Toll_Free: 888-509-1970 email: support@fieldServer.com

Image 8
Contents MetOne Particle Counters Applicability & EffectivityTable of Contents MetOne Particle Counter Serial Description FS-8700-123 MetOne Particle Counter Serial Driver Manual Hardware Connections Hardware Connection Tips / Hints RS-232 PortConfiguring the FieldServer as a MetOne PC Serial Client Data Arrays/DescriptorsHF CNC Client Side Connection DescriptionsClient Side Node Descriptors Driver Related Map Descriptor Parameters Timing ParametersDatimes Rdbc MET1 Map Descriptor Example 3 Read the operating mode Datimes Wrbx MET1Map Descriptor Example 4 Start / Stop Counting Map Descriptor Example 5 Change Mode Map Descriptor Example 6 Select Device Map Descriptor Example 7 Read the Current Record Map Descriptor Example 8 Dumping the Current Record DACURRD01LBL ,0 Map Descriptor Example 10 Reading from a SubDevice/Port Map Descriptor Example 11 Selecting a Sub-Device/Port Configuring the FieldServer as a MetOne PC Serial Server Appendix A. Driver Error Messages Page Appendix A.1. Driver Operating and Error Statistics FYIAppendix A.2. Driver Exposed Operating and Error Statistics UINT32Page This page Intentionally Left Blank