ETA Systems specifications ETA-20SH Specifications

Page 15

 

ETA-20SH

AC Power Conditioning & Suppression Module

ETA-20SH SPECIFICATIONS

 

General

 

Type

AC Power Conditioner & Suppressor Module

Power Requirements

120V 60Hz

Power Consumption

.5W

RoHS Compliant

Yes

Panel

 

Switched Outlets

Two, 20A

Spike & Surge Suppression

H-N, N-G, H-G

Manual Override

Slide switch

Extreme Voltage Shutdown

(EVS) Below 101V or Above 132V AC Line (When Used With ETA-ECS6RM)

Connectors

5 Position Phoenix Euro Block Style

Fuse Protection

20A Slow Blow

DCV Remote Trigger

5 – 24DCV

Remote Trigger

SPST Contact

Status Signals

Output for Voltage and Current Data (All Signals are Low Voltage and Low Current)

Indicators

Incoming AC, Active, AC Fault

Power Cord

9' (3M), 12-gauge NEMA 5-20P 125v AC plug

Technical Data

 

Current Rating

20 amps

Operating Voltage

102 to 132 VAC

High Voltage Surge Protection

Trigger at 133VAC, 1ms Typically (When Used With ETA-ECS6RM)

Spike & Surge Suppression

H-N, N-G, H-G

Low Voltage Protection

Trigger 101 VAC, 1ms Typically (When Used With ETA-ECS6RM)

Spike Protection Modes

Circuitry on Incoming AC Mains.

Minimum Spike Clamping Voltage

460 VRMS @ 3,000 amps

Maximum Spike Clamping Voltage

6000v

Maximum Spike Clamping Response Time

1 nanosecond

Spike Clamping Voltage @ 100A

1250Vp for 20µs

Maximum surge current

6,500 amps

Energy Rating @ 2ms

600 Joules

Noise Attenuation EMI/RFI Sequencer

10dB @ 10kHz, 40dB @ 100kHz, 100dB @ 10MHz

Temperature Range

5° to 35°C

Humidity Range

5% to 95% R.H.

Mechanical

 

Chassis Finish

Black

Mounting

Side bracket adjustable

Dimensions

3.0" H x 8.5" D x 3.5" W (76mm x 216mm x 89mm)

Weight

5.5lbs (2.49kg)

Agency Listings

MET (UL1449 Code)

1601 Jack McKay Blvd. • Ennis, Texas 75119 U.S.A.

Telephone: 800-321-6699 • Fax: 800-996-3821

– 15 –

ETAsys.com

Specifications are subject to change without notice.

Image 15
Contents ETA-20SH Table of Contents AC Power Conditioning & Suppression ModuleKEY Features IntroductionApplications ETA-20SH Safety Instructions EVS Protection EMI/RFI FiltersAC Spike Protection AC Surge ProtectionAC Mains Power Cord 9 3m, 12-gauge Panel FeaturesWiring with AN ETA-ECS6RM Sequencer Controller ECM Data Wire and DistanceUsing the ETA-20SH AS a Standalone Unit Remote Activation VIA Switch or DCV TriggerETA-ECS6RM Sequencer Controller Interface with ETA-20SH Single ETA-ECM20 Control PortRelay Contacts Wiring With an ETA-ECS3 Sequencer Controller Troubleshooting the ECM Module AS a Standalone Unit Troubleshooting the ECM Module with AN ETA-ECS3 Issue 1 Incoming AC LED on the ECM is not illuminated Troubleshooting the ECM Module with AN ETA-ECS6RMIssue 6 No Voltage Reading at the ETA-ECS6RM ETA-20SH Specifications Service Limited Warranty