AC Power Conditioning & Suppression Module
TROUBLESHOOTING THE ECM MODULE WITH AN ETA-ECS6RM
Note: All troubleshooting should be done by a certified electrician.
Issue 1: Incoming AC LED on the ECM is not illuminated.
Possible Cause #1 Incoming AC Mains circuit breaker has tripped due to excessive load.
Action Needed Check the AC outlet that the
Possible Cause #2 AC Mains power is ok (120V), internal 20A
Issue 2: AC Fault LED is Flashing on the ECM.
Possible Cause Although the Clamping Suppression circuit virtually assures protection from most transient voltage spikes and surges, nature has a way of occasionally creating electrical forces that are beyond the capabilities of any device to absorb without some degree of damage. In the rare instance that this occurs, the clamping circuit can be damaged during the suppression.
Action Needed The unit will need to be repaired or replaced. It is important to have all equipment that was connected to that
Note: The unit will still operate but no AC Spike or Suppression protection will be available.
Issue 3: Unit is set to External Trigger, the incoming AC LED is illuminated but the Active LED is not illuminated.
Possible Cause #1 External DCV from the
Possible Cause #3 External DCV voltage is too low to activate the trigger circuit. Must be a minimum of 5VDC to activate the ECM module. Possible short in the wiring system.
Issue 4: ECM Active LED is not illuminated, Incoming LED is illuminated but the Abnormal LED on the
Possible Cause The AC Mains Voltage exceeded 127VAC or the voltage dropped below 107VAC activating the “EVS” shutdown.
Action Needed The
Note: It is important to have all equipment that was connected to that
Issue 5:
Possible Cause The AC Mains Voltage at the ECM Module reached between
Action Needed The
Note: It is important to have all equipment that was connected to the module inspected for proper operation. If the problem persists, contact your local power company for the cause of unstable AC line conditions.