Minuteman UPS MCP 2000i, MCP 3000i, MCP 1000i user manual MCP Acceptable Input Voltage

Page 20

NOTE: 230VAC Specs Shown In ( )

MCP 1000

 

MCP 2000

 

MCP 3000

 

(MCP 1000i)

 

(MCP 2000i)

 

(MCP 3000i)

Acceptable Input Voltage

 

 

0-138 (0-275 VAC)

 

Input Voltage (on-line operation)

 

 

88-138 (160-275 VAC)

 

Power Factor

 

>0.97

 

 

 

Output Voltage (on-line operation)

120VAC

 

120VAC

 

120VAC

 

(220/230/240 VAC)

 

(208/220/230/240 VAC)

 

(208/220/230/240 VAC)

Transfer time

 

 

0ms (true-on-line)

 

Maximum Load

1000VA/700W

 

2000VA/1400W

 

3000VA/2100W

Voltage regulation

 

±2%

 

 

 

Nominal input frequency

 

 

50 or 60Hz auto-sensing

 

Input protection

 

Manual reset circuit breaker

 

Frequency limits (on-line operation)

 

 

50 or 60Hz ±2Hz

 

T H D

 

3%(Linear load); 6%(Rectifier load)

Slew Rate

 

 

1 Hz/sec

 

Overload capacity

105%-125% for 3 min., 125%-150% for 30 sec., > 150% for 1 sec.

Crest factor

 

3:1

 

 

 

Efficiency

80%

 

83%

 

 

85%

On-battery Output Voltage

 

 

120 VAC (230 VAC) ±2%

 

On-battery frequency

50 or 60Hz ±1 Hz unless synchronized to utility during brownout

On-battery wave shape

 

 

True sinewave

 

Protection

Over-current and short circuit protected, latching shutdown on overload

Surge energy rating

 

 

480J

 

(one time 10/1000ms waveform)

 

 

 

 

 

 

Surge current capability (one time, 8/20ms

 

 

6500 A maximum

 

waveform)

 

 

 

 

 

 

Surge response time

0ns (instantaneous) normal mode, <5ns common mode

Surge voltage let through

 

 

< 0.3% of peak, typical

 

 

(percentage of applied ANSI C62.41 cat A ±6V test wave form)

10 Base-T surge protection let-through

 

<5%

 

 

 

 

(As a percentage of an applied ±6kV 1.2/50ms, 500A 8/20ms test)

Telephone line surge protection let-through

 

<1%

 

 

 

 

(As a percentage of an applied ±6kV 1.2/50ms, 500A 8/20ms test)

Noise filter

Normal and common mode EMI / RFI suppression

Input(standard)*

6ft. NEMA 5-15P

 

6ft. NEMA 5-30P

 

6ft. NEMA 5-30P

 

(IEC 320 C-14)

 

(IEC 320 C-14)

 

(IEC 320 C-20)

Output receptacles(standard)*

6 x NEMA 5-15R’s

 

4 x NEMA 5-15R’s and

 

4 x NEMA 5-15R’s and

 

4-Battery back-up

 

 

 

 

1 x L5-30R

 

1 x L5-30R

 

2-Surge protected only

 

 

 

 

(6 x IEC 320 C-13’s)

 

(6 x IEC 320 C-13’s)

 

(4 x IEC 320 C-13’s)

 

 

 

 

 

 

 

 

Communication ports

2-female DB-9’s(1-RS232 and 1-Dry Contact )

Battery type: Spill proof, maintenance free,

4 x 12V7AH

 

6 x 12V7AH

 

8 x 12V7AH

sealed lead acid

 

 

 

 

 

 

Battery Pack

N/A

 

Optional

 

Optional

Typical battery life

3 to 5 years depending on number of discharges and ambient temperature

Typical recharge time

 

2 to 4 hours from 50% discharge

 

Operating temperature

0 to 40 degrees C (+32 to 104 degrees F)

Storage temperature

-15 to +45 degrees C ( +5 to +113 degrees F)

Operating and storage relative humidity

 

 

0 to 95% non-condensing

 

Operating elevation

 

0 to +3,000 m (0 to +10,000 ft.)

 

Storage elevation

 

0 to +15,000 m (0 to +50,000 ft.)

 

Electromagnetic immunity

IEC 801-2 LEVEL IV, 801-4 LEVEL IV, 801-5 LEVEL III

Audible noise at 1 m (3ft.)

 

 

<45 dBA

 

Size (H x W x D)

32.2 x 18.8 x 40.5 cm

 

32.2 x 18.8 x 47.6 cm

 

32.2 x 18.8 x 55.5 cm

 

(12.7 x 7.4 x 15.9 in.)

 

(12.7 x 7.4 x 18.7 in.)

 

(12.7 x 7.4 x 21.9 in.)

Weight- Net (shipping)

20(24)Kg

 

28(32)Kg

 

39.2(42.7)Kg

 

44.1(52.9) lbs.

 

61.7(70.6) lbs.

 

86.4(94.2) lbs.

Safety and approval

Listed to UL 1778 Compliance to CSA 22.2; (TUV/GS)

EMC Verification

FCC Class A (2,3KVA) Class B (1KVA); (CE; TUV/EMC)

*Options available. N/A for MCP 1000(i)

All specifications subject to change without notice.

18

Image 20
Contents MCP Series Page MCP Series User’s Manual Explanation of Symbols Important Safety Instructions Receiving Inspection Please Save the Packing MaterialsPara Systems Life Support Policy Front Panel Power SwitchLED Indicators Rear Panel MCP 1000i Rear Panel MCP 2000 Rear Panel MCP 2000i Rear Panel MCP 3000 Rear Panel Installation Placement Computer Interface Connections OUT a ConnectionTurning the Unit ON/OFF Communication Interface HardwareTroubleshooting Chart Symtom Possible Cause What To DoReplacing the Batteries Battery pack connection UPSIf the UPS Requires Service MCP Acceptable Input Voltage Limited Product Warranty Except AS Provided HEREIN, Para Systems Makes no WarrantiesPage Page 34000130 REV

MCP 1000, MCP 3000i, MCP 2000i, MCP 2000, MCP 3000 specifications

The Minuteman UPS product line offers a range of uninterruptible power supplies designed to protect critical equipment from power disturbances. The models MCP 1000i, MCP 2000, MCP 2000i, MCP 3000, and MCP 3000i provide reliable backup power and advanced features that ensure continuous operation for sensitive electronics used in both home and business environments.

Starting with the MCP 1000i, this model features a capacity of 1000 VA and is equipped with line-interactive technology. This ensures that it can automatically adjust to power fluctuations without switching to battery mode, which prolongs battery life. With a user-friendly LCD interface, users can easily monitor voltage levels and battery status, ensuring peace of mind in critical situations.

The MCP 2000 and MCP 2000i models increase power capacity to 2000 VA. Both variants offer similar functionalities, but the ā€œiā€ version integrates an advanced LCD display for enhanced monitoring capabilities. They come equipped with multiple outlets, allowing users to connect various devices while maintaining protection against surges and outages. Both versions boast high-efficiency operation, which minimizes energy waste and reduces operating costs.

Moving to the MCP 3000 and MCP 3000i models, these UPS units are designed for larger power demands, offering 3000 VA capacity. The MCP 3000 maintains a line-interactive topology, providing continuous protection against brownouts and voltage spikes. The augmented MCP 3000i boasts an advanced LCD interface, providing real-time information and alerts, allowing users to diagnose issues quickly and effortlessly. This series is suitable for powering critical servers, networking equipment, and high-performance workstations.

Key features across all models include an energy-saving Green Mode, which maximizes efficiency by reducing energy consumption. They also incorporate Smart Battery Management, which enhances battery performance and longevity through intelligent charging and discharging cycles. Robust surge protection helps safeguard devices against transient voltage spikes.

These Minuteman UPS systems are designed with user convenience in mind, featuring hot-swappable batteries for effortless maintenance without shutting down connected devices. Overall, the MCP series provides reliable power protection, advanced technology, and user-friendly features, making them suitable solutions for both home and professional environments in need of uninterrupted power.