SSI
|
|
| ERP2U Power Supply Design Guide, V2.31 | |
| 1 | SMBus Clock | White/Green Stripe |
|
|
|
|
|
|
2 | SMBus Data | White/Yellow Stripe | ||
|
|
|
|
|
3 | SMBAlert |
|
| |
|
|
|
|
|
4 | ReturnS | Black/White Stripe | ||
|
|
|
|
|
| 5 | 3.3RS | Orange/White Stripe | |
|
|
|
|
|
6.2Grounding
STATUS
Required
The ground of the pins of the power assembly wire harness provides the power return path. The wire harness ground pins shall be connected to safety ground (power supply enclosure).
6.3Remote Sense
STATUS
Optional
The power assembly may have remote sense for the +3.3V (3.3VS) and return (ReturnS) if the Optional Server Signal connector is implemented and the module has a +3.3V output. The remote sense return (ReturnS) is used to regulate out ground drops for all output voltages. The +3.3V remote sense (3.3VS) is used to regulate out drops in the system for the +3.3 V output. The remote sense input impedance to the power
6.4Output Power/Currents
STATUS
Recommended
The following tables define the power and current ratings for different recommended power levels. Depending upon the system design, the power supply modules may have less outputs than required by the system (example: +12V and 5VSB). If there are less outputs than required by the system on the module, the cage shall have additional DC/DC converters to generate the voltages not produced by the modules (example: +12V/+5V, +12V/+3.3V,
Voltage
+3.3 V 7
+5 V 7
Table 13: 550 W Load Ratings
Minimum Continuous | Maximum Continuous |
0.8 A | 24 A |
0.5 A | 24 A |
- 18 - |
|
Peak