Panasonic FP-X Series manual  Relay output specifications control units, expansion units

Page 22

FP-X series

Specifications

Input specifications (control unit, expansion unit and add-on cassette)

 

Item

 

Description

 

 

Relay output (control unit and expansion unit)

Transistor output (control unit and expansion unit)

Add-on cassette (AFPX-IN8, AFPX-IN4T3)

Insulation method

 

Photocoupler

 

 

 

 

 

 

Rated input voltage

 

24VDC

 

Operating voltage range

 

21.6 to 26.4VDC

 

 

 

 

 

 

 

 

Approx. 4.7mA (Control unit X0 to X7)

Approx. 8mA (Control unit X0 to X3)

 

 

 

 

 

Rated input current

 

Approx. 4.7mA (Control unit X4 to X7)

Approx. 3.5mA

Approx 4.3mA (Control unit X8 and after, Expansion unit)

 

 

 

 

 

 

Approx. 4.3mA (Control unit X8 and after, Expansion unit)

 

 

 

 

 

 

Input points per common

8 points/common (C14, E16) 16 points/common (C30, C60, E30)

8 points/common (AFPX-IN8), 4 points/common (AFPX-IN4T3)

 

 

 

 

(Input power polarity either positive or negative)

 

 

 

 

 

 

 

 

 

 

Min. ON voltage/ON current

19.2V/3 mA

19.2V/6mA (Control unit X0 to X3)

19.2V/3mA

19.2V/3mA (Control unit X4 and after, Expansion unit)

 

 

 

 

Max. OFF voltage/OFF current

2.4V/1 mA

2.4V/1.3mA (Control unit X0 to X3)

2.4V/1mA

2.4V/1mA (Control unit X4 and after, Expansion unit)

 

 

 

 

 

 

Approx. 5.1k7 (Control unit X0 to X7)

Approx. 3k7 (Control unit X0 to X3)

Approx. 6.8k7

Input impedance

Approx. 5.1k7 (Control unit X4 to X7)

Approx. 5.6k7 (Control unit X8 and after, Expansion unit)

 

 

Approx. 5.6k7 (Control unit X8 and after, Expansion unit)

 

 

 

 

Control unit X0 to X3

 

 

 

Control unit X0 to X7

135Μs or less: Nominal input

 

 

 

0.6ms or less: Normal input

5Μs or less: High-speed counter, pulse catch,

 

 

 

interruption input setting*1

 

 

OFF μ ON

50Μs or less: High-speed counter, pulse catch,

Control unit X4 to X7

1.0ms or less

Response

interruption input setting *1

135Μs or less: Nominal input

 

 

 

 

time

 

Control unit X8 and after, Expansion unit

50Μs or less: High-speed counter, pulse catch,

 

 

 

interruption input setting*1

 

 

 

0.6ms or less

Control unit X8 and after, Expansion unit

 

 

 

 

 

 

 

 

0.6ms or less

 

 

OFF μ ON

Same as above

1.0ms or less

 

 

 

 

 

Operating indicator

 

LED display

 

 

 

 

 

 

Note: *1 Specification at the rated input voltage of 24VDC, 25°C.

Relay output specifications (control units, expansion units)

Item

Description

Output type

1a contact

Rated control capacity (Resistive load)

2A 250VAC, 2A 30VDC (8A or less/common)

Output points per common

C14, E16: 1 point or 3 points/common, C30, E30: 1 point or 4 points/common, C60: 1, 2 or 4 points/common

Response time

OFFμON

Approx. 10ms

ONμOFF

Approx. 8ms

 

 

 

Life time

Mechanical

20 million operations or more (Operation frequency 180 times/min)

 

 

Electrical

100,000 operations or more (Operation frequency 20 times/min at the rated control capacity)

 

 

 

 

Surge absorber

None

 

 

 

Operating indicator

LED display

 

 

 

Transistor output specifications (Control unit, expansion unit and add-on cassette)

Item

 

 

Description

 

 

 

Control unit, Expansion unit

Add-on cassette (AFPX-TR8, AFPX-TR6P, AFPX-IN4T3)

 

 

 

 

Insulation method

 

 

Photocoupler

 

Output type

 

 

Open collector

 

Rated load voltage

 

 

NPN type: 5 to 24VDC, PNP type: 24VDC

24VDC

Load voltage allowable range

NPN type: 4.75 to 26.4VDC, PNP type: 21.6 to 26.4VDC

21.6 to 26.4VDC

Max. load current

 

 

0.5A

NPN type: 0.3A, PNP type: 0.5A

 

 

 

 

 

 

Max. inrush current

 

 

1.5A

 

 

 

 

 

Output points per common

C14: 6 points/common, E16: 8 points/common, C30, C60, E30: 8 or 6 points/common

TR8: 8 points/common, TR6P: 6 points/common, IN4T3: 3 points/common

 

 

 

 

OFF state leakage current

1ΜA or less

 

 

 

 

 

 

 

ON state voltage drop

 

 

0.3VDC or less

1.5VDC or less

 

 

 

 

 

 

Response time

OFF

μ

ON

1ms or less*2

0.1ms or less

OFF μ ON

1ms or less*2

0.8ms or less

 

Voltage range for external power supply

21.6 to 26.4VDC

 

 

 

 

 

 

Surge absorber

 

 

Zener diode

 

 

 

 

 

 

 

Operating indicator

 

 

LED display

 

 

 

 

 

 

 

Note: *2 Please refer to the user manual for Y0 to Y7 of the transistor output type.

01/2008

22

Image 22
Contents FP-X Series  Independent comment memory  High-speed operation Large capacity program memory  Maximum number of I/O pointsPositioningPositioning  Expansion unit Highly expandable lineup satisfies a wide range of demands Control unit  Add-on cassetteFP-X series Name and function of each partUp to 8 expansion units E16R, E30R, EFP0 can be connected High capacity, ultra high-speed processingMax channels Product number Specifications Great expandabilityAttachment position see the table above Add-on cassette lineupMax. number of at- tachable cassettes Add-on Cassette Part number Application Add-on cassette EthernetData collection Program / monitoringMechanisms PositioningSimultaneous control  Built-in 4-axis pulse output Transistor output typeMulti-point PID control Target valueBefore Reassuring data securityWith FP-X  Modbus-RTU compatibility Network PLC link MEWNET-W0  Another available applicationBattery holder Connector Backup battery for FP-X AFPX-BATT  F-ROM data saving data can be saved without a batteryOther useful functions Most important highlights at a glance Programming according to the international standard IECPart numbers  FP-X control unit Product number list FP-X expansion unit  FP-X options and service parts  FP-X add-on cassette FP0 intelligent units  FP0 expansion units FP0 link units  FP memory loader Specifications Programmable display GT series  Fpwin pro PLC programming software according to IECWeight  General specifications Power consumption, weight Description Control specifications  Relay output specifications control units, expansion units  FP-X control unit dimensions unit mm Dimensions FP-X expansion FP0 adapter dimensions unit mm Please contact our Global Sales Companies