FP-X series

Add-on cassette (Ethernet)

This Ethernet cassette fulfills user requiremens such as the “easy collection of inspection/ production data” or “remote changing of ladder programs”, using LAN (Ethernet).

The industry’s first*¹ add-on to equip a compact PLC with an Ethernet port

AFPX-COM5

Ethernet RS232C

*1: In Japan, as of May 1, 2007

Enables easy Ethernet connections with a compact PLC, which were previously not possible.

Also equipped with an RS232C port. Together with the tool port (programming port), a total of 3 communication ports are available, which is remarkable for a compact PLC.

For example, the following operations are simultaneously available with this cassette attached:

1.I/O control

2.Reading data from a tester (measuring instrument) of inspection equipment (RS232C)

3.Collecting the read data from the host computer (Ethernet)

4.Setting/monitoring via a touch panel (Tool port)

Application

Data collection

Remote maintenance

Operation data managing software

Program / monitoring

PCWAY

 

Touch panel

 

Ethernet

Programming software

 

 

 

 

 

 

FPWIN GR

 

 

 

FPWIN Pro

 

Tool port

Tool port

Tool port

Internet connection

 

 

 

 

 

Ethernet

Ethernet

RS232C

RS232C

RS232C

 

 

Touch

Touch

 

 

panel

panel

 

Measuring

Measuring

Measuring

 

instrument

instrument

instrument

 

Interface

Specifications and functions

 

 

 

10BASE-T, 100BASE-TX, TCP/IP, Baud rate: 9600bps/115200bps

Ethernet

MEWTOCOL-COM master/slave (3 connections max.)

(COM1)

General- purpose serial communications (1 connection max.)

 

Server function, client function

 

 

 

3-wire (RD, SD, SG), Asynchronous,

RS232C

Baud rate: 300bps to 115200bps

MEWTOCOL-COM master/slave

(COM2)

General-purpose serial communications

 

 

Modbus-RTU master/slave

 

 

Use our free software “Configurator WD” for setting up the Ethernet port (e.g. IP address and operation mode).

Download the software free of charge from:

http://www.panasonic-electric-works.com

Ethernet port

 

Specifications

functions

 

 

 

 

 

 

 

 

 

 

Automatically sends responses without communica-

MEWTOCOL-COM

tion programs to commands of Matsushita’s open

protocol “MEWTOCOL”.

master/slave

 

 

Contact/word data writing/reading, program editing

 

 

 

 

 

 

PCWAY, FPWIN GR and FPWIN Pro are supported.

 

 

 

 

General

 

Server

Waits for a connection from a client PC (personal

 

computer), and after the connection has been estab-

purpose

 

function

 

lished, receives data from the PC.

serial

 

 

 

 

 

communi-

 

Client

After the power has been turned on, establishes a

cations

 

 

function

connection to a preset IP address and sends data.

 

 

 

 

 

 

01/2008

Image 9
Contents FP-X Series  Large capacity program memory  High-speed operation Independent comment memory  Maximum number of I/O pointsPositioningPositioning  Control unit Highly expandable lineup satisfies a wide range of demands Expansion unit  Add-on cassetteName and function of each part FP-X seriesHigh capacity, ultra high-speed processing Up to 8 expansion units E16R, E30R, EFP0 can be connectedMax channels Great expandability Product number SpecificationsMax. number of at- tachable cassettes Add-on cassette lineupAttachment position see the table above Add-on Cassette Part numberData collection Add-on cassette Ethernet Application Program / monitoringSimultaneous control PositioningMechanisms  Built-in 4-axis pulse output Transistor output typeTarget value Multi-point PID controlReassuring data security BeforeWith FP-X  PLC link MEWNET-W0 Network Modbus-RTU compatibility  Another available application F-ROM data saving data can be saved without a battery Battery holder Connector Backup battery for FP-X AFPX-BATTOther useful functions Programming according to the international standard IEC Most important highlights at a glancePart numbers Product number list  FP-X control unit FP-X expansion unit  FP-X add-on cassette  FP-X options and service parts FP0 expansion units  FP0 intelligent units FP0 link units  Programmable display GT series Specifications FP memory loader  Fpwin pro PLC programming software according to IEC Power consumption, weight  General specificationsWeight Description Control specifications  Relay output specifications control units, expansion units Dimensions  FP-X control unit dimensions unit mm FP-X expansion FP0 adapter dimensions unit mm Please contact our Global Sales Companies