Item | Description | |
Rated voltage | 100 to 240VAC (AC power), 24VDC (DC power) | |
Operating voltage range | 85 to 264VAC (AC power), 20.4 to 28.8VDC (DC power) | |
Service power output | C14: 24VDC/0.15A, C30 and C60: 24VDC/0.4A | |
Rush current | 40A or less (C14), 45A or less (C30, C60) at 25°C (AC power) | |
12A or less at 25°C (DC power) | ||
| ||
|
| |
Allowed momentary power off time | 110ms or more | |
Ambient temperature | 0 to +55°C | |
|
| |
Storage temperature | ||
Ambient humidity | 10 to 95% RH (at 25°C, | |
Storage humidity | 10 to 95% RH (at 25°C, | |
| Combined input/output terminals - Combined power and ground terminals, | |
| 2300VAC*1 1 minute (AC power), 500VAC*1 1 minute (DC power) | |
Breakdown voltage | Input terminals - Relay output terminals, 2300VAC*1 1 minute | |
Input terminals - Transistor output terminals, 500VAC*1 1 minute | ||
| ||
| Power terminals - Ground terminals, 1500VAC*1 1 minute (AC power), | |
| 500VAC*1 1 minute (DC power) | |
| Combined input/output terminals - Combined power and ground terminals, | |
| 100M7 or higher (500VDC using an insulation resistance meter) | |
Insulation resistance |
| |
Input terminals - Output terminals, 100M7 or higher (500VDC using an insulation resistance meter) | ||
| ||
|
| |
| Power terminals - Ground terminals, 100M7 or higher (500VDC using an insulation resistance meter) | |
|
| |
Vibration resistance | 5 to 9Hz, single amplitude 3.5mm/9 to 150Hz, constant acceleration 9.8m/s2, | |
1 sweep/min, 10 sweeps in each XYZ direction | ||
| ||
|
| |
Shock resistance | 147m/s2, 4 times on 3 axes | |
| 1500V | |
Noise immunity | 500V | |
(per noise simulator method) (power terminals) | ||
| ||
|
| |
Operating condition | No corrosive gas and no excessive dust | |
EC Directive Compliance Standard | Conforming to | |
Level of contamination | 2 | |
II | ||
Note: |
| |
*1 Cutoff current 5mA |
|
Power consumption, weight
Product name | Part number | Current consumption | Weight | |
| 26W or less*2 | Approx. 280g or less | ||
Control Unit | 52W or less*2 | Approx. 490g or less | ||
| 64W or less*2 | Approx. 780g or less | ||
Expansion I/O Unit | 8W or less*2 | Approx. 195g or less | ||
45W or less*2 | Approx. 470g or less | |||
| ||||
Expansion FP0 adapter | 0.24W or less*3 | Approx. 65g | ||
Input cassette | 1W or less*2 | Approx. 25g | ||
Output cassette | 1W or less*2 | Approx. 25g | ||
1W or less*2 | Approx. 25g | |||
| ||||
Pulse I/O cassette | 2W or less*2 | Approx. 25g | ||
Master memory cassette |
| 2W or less*2 | Approx. 20g | |
Analog input cassette | 2W or less*2 | Approx. 25g | ||
Analog I/O cassette | 3W or less*2 | Approx. 25g | ||
Analog output cassette | 5W or less*2 | Approx. 25g | ||
Thermocouple input cassette | 1W or less*2 | Approx. 25g | ||
|
|
| ||
|
|
|
| |
|
| Approx. 20g | ||
|
| 2W or less*2 | ||
Communication | ||||
|
| |||
cassettes |
|
|
| |
|
| |||
|
|
| ||
|
|
|
| |
| 3W or less*2 | Approx. 25g | ||
| 2W or less*2 | Approx. 20g |
Notes:
*2 Power consumption by the AC power supply connected to the control unit
*3 Power consumption by the DC power supply connected to the expansion FP0 adapter Please refer to the user manual and specifications for further details.
01/2008
20