operation on battery
no utility power
break in utility power
0 mn
1a to 1d indicating the remaining battery time: here, between 75 and 87%
1e flashing
1f on
1 beep every 10 s
your load is supported by the battery
warning alarm at low battery
x mn
1a to 1c off
1d flashing
1e flashing
1f on
1 beep every 3 s
you have less than 12% battery time remaining: power down your load, Pulsar will soon switch off automatically
Pulsar switches off automatically
x + ε mn
1a to 1f off
silence
UPS output "off"
return of utility power
At whatever point the utility power returns, Pulsar switches to normal operation:
1a to 1d indicating the battery recharge percentage: here, between 12 and 25%
1e indifferent
1f on
silence
your load is supplied by the utility power (on line)
Note 1:
The "function" button is to deactivate or activate the audio warning device when operating on battery, or when site wiring fault occured.
Note 2:
The "function" button allows you to force a transfer on bypass (push three times within 5 seconds) and to come back on normal operation (push again three times within 5 seconds).
load charge percentage
If utility power is present, hold alarm silence button in:
1a to 1d indicating the load charge percentage: here 50%
1e off
1f on silence