communication
cthe
MGE UPS SYSTEMS.
The
standard port
RD TD
0V
5 | 4 | 3 | 2 | 1 |
9 8 7 6
With the EX Driver software program you can set up Pulsar EX to suit your user conditions (EX Tuner), supervise your UPS and safeguard your system (UPS Manager 3.1). To install EX Driver, connect the serial cable supplied to COM1 to COM4 (set up by EX Tuner) series port of your computer equipped with Windows 3.1 on the one end, and to the serial Pulsar EX connector on the other end. Insert the disk and type A:\Install. Follow the installation instructions on the screen. You may then use 2 software programs :
vEX Tuner to set up Pulsar EX,
vUPS Manager 3.1 to supervise and safeguard your system.
option 1
cstatus information card: after the card is installed in the rear of the Pulsar, communication port transmits the status information on a
1 | - | ground, |
2 | - | remote power off, |
4 | - | normal operation, |
5 | - | common, |
6- operation on utility power,
7- low battery warning,
8- load supplied by UPS,
9- operation on battery.
| 0V |
|
|
|
|
|
| 5 | 4 | 3 | 2 | 1 | 12 |
|
| 9 | 8 | 7 | 6 | |
|
|
| ||||
n.c. | n.o. |
| n.o. |
| n.o. | n.o. |
| 0V |
| 0V |
| 0V | 0V |
Relay breaking capacity:
Vmax = 25V DC
Imax = 10mA
n.o. : normally open,
n.c. : normally closed.
Note for remote power off information: Remove first J1 jumper on the status information board, then link your remote power off switch S1 between pins 2 and 5. Follow instructions from user's manual of the
optional board for installation.
cswitch ON: normal operation,
cswitch OFF: unit stops immediatly.
5 | 4 | 3 | 2 | 1 | 12 |
| 9 | 8 | 7 | 6 | |
|
|
S1
option 2
cSNMP card: after the card is installed in the rear of the Pulsar, the communication port transmits information supported by the SNMP protocol on an RJ45 or BNC connector.
Contact your sales agent for further details.
MGE UPS SYSTEMS | Pulsar EX: | 13 |