MGE UPS Systems 6000 manual Environment conditions, Protection, UPS not including battery, Ups

Page 10

MGETM GalaxyTM 6000 : Specification guide

Parallel UPS, three-phase, 250 to 3000 kVA*

* Power rating for an N+1 redundant configuration

7 - Environment conditions

7.1 - UPS (not including battery)

7.1.1 - Operation

The UPS, not including the battery, shall be capable of operating under the following environmental conditions without loss of performance:

ωambient temperature range: 0° C to +40° C.

ωrecommended temperature range: +20° C to + 25° C;

ωmaximum temperatures: 40 °C for 8 hours

ωmaximum relative humidity: 95% at 25° C;

ωmaximum altitude: 1000 meters.

7.1.2 - Storage

The UPS, not including the battery, shall be designed for storage under the following conditions:

ωambient temperature range: -10° C to +45° C.

8 - Protection

8.1 - UPS

Each UPS unit shall include protection against AC-source overvoltages (as per standard IEC 60146), excessive external or internal temperature rise and vibrations and impacts during transport.

8.2 - Rectifier and charger

Each rectifier/charger shall be equipped to receive an external order to automatically shut down under the following circumstances:

ωemergency off; in this case, the shutdown will be accompanied by opening of the battery circuit breaker;

ωbattery room ventilation fault.

The rectifier and the charger shall automatically shut down if the DC voltage reaches the maximum value specified by the battery manufacturer.

8.3 - Inverter

The load shall be protected against any overvoltages that could result from voltage regulation failure at the output of the inverters.

The inverter (and the corresponding rectifier/charger) shall automatically shut down if the DC voltage reaches the minimum value specified by the battery manufacturer.

Each inverter shall be equipped with an automatic shutdown system to protect its power circuits against overloads exceeding UPS-system overload capacity when bypass power is not available. In particular, a short-circuit on the load shall initiate a static shutdown of each inverter, without blowing a fuse.

8.4 - Batteries

8.4.1 - Protection against deep discharge and self-discharge

The UPS shall comprise a device designed to protect the battery against deep discharges, taking into account the characteristics of the discharge cycles, with isolation of the battery by a circuit breaker.

8.4.2 - Independent regulation and monitoring systems

A regulation system shall regulate the battery voltage and the charge current.

A second system, independent of the regulation, shall monitor the battery voltage and the charge current. Consequently, if the regulation system fails, the monitoring system steps in to shut down the charger and avoid overcharging.

8.4.3- Regulation of the battery voltage depending on the ambient temperature

A temperature sensor adapts the charge voltage to the ambient temperature.

This regulation system takes into account the chemical reaction and prolongs the battery service life. The permissible temperature range is set in the personalisation parameters.

An alarm shall be issued for temperatures outside the permissible range.

8.4.4- Self-test

Battery monitoring shall be carried out by an automatic device. Self-test intervals shall be set to one month by default, but shall be adjustable.

This self-test system shall, where necessary, initiate indications via LEDs on the front panel or a message to a remote monitoring system.

APC By Schneider Electric

Edition - 03/2009

Spec. E - 10

Image 10
Contents Power rating for an N+1 configuration Contents Purpose UPS definitionBrief description Operating principle Sizing and general characteristics Electrical characteristics AC sources Batteries InverterStatic bypass Discrimination and short-circuit capacityMechanical characteristics Protection UPS not including batteryEnvironment conditions UPSDigital battery monitoring Battery managementMeasurement of actual backup time Self-testGraphic display User interface and communicationUser interface ControlsMaintainability Local and remote diagnostics and monitoring E. ServicesCommunication Test procedures and quality system Standards and testsWarranty ServicesInstallation services Electrical diagram UPSCentralized bypass UPS system with centralized bypass up to six unitsAppendix. Comparison table BatteryBattery management and protection Type of UPSEfficiency InverterStatic bypass User interfaceCertification ServicesCommunication Operation, Maintainability